Permit Information
Permit NumberELE03-02645
StatusFinaled
Name DAVID CHENOWETH
Site Address 1816 S BROXON ST
Project Name 
Customer Number 
ePlanReview 
Description
the landlord for broxon
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/2/20039/2/20039/2/2003APASS
DetailsJim Schmer
Permanent Service8/29/20039/2/20039/2/2003APASS
DetailsJim Schmer
david; Phone #: ###-#### Internet Inspection Request from: Barbara Moore p/s o/h rec - ok 9/2/2003 9:52:44 AM
Final8/28/20038/29/20038/29/2003AFAIL
DetailsJack Frank
dave; Phone #: ###-#### Internet Inspection Request from: Annette Moore Jim this is the homeowner I called you about 230.24(A) exception 3 needs 18 inches clearence drop over roof 200.6(A), 300.3(A)$(B) B.C.C. 4-5-54 code violations not to be retained 8/28/2003 3:01:40 PM
Final8/29/20038/29/20038/29/2003PFAIL
DetailsJack Frank
david; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie no final conference only Jim and I met with owner 8/29/2003 12:42:35 PM
Permanent Service8/27/20038/27/20038/27/2003PFAIL
DetailsJack Frank
david; Phone #: ###-#### Internet Inspection Request from: Marc Lileks cor. posted met with owner 250.52(A)(1),or104(A) grd or bond water system 310.15 proper breaker size for #10, #8, needs 200 amp wire for 200 amp p/s, 250.140,142,134(A) dryer type se or 10/3, 230.24(B) service drop clearence, 408.4 label panel, hot tub shall be wired by electrical contractor remove wiring done by owner 8/27/2003 1:15:15 PM