Final | 10/10/2003 | 10/10/2003 | 10/10/2003 | P | PASS |
Jack Frank
|
|
|
ROGER; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok cor. made see added p/s 10/10/2003 1:06:17 PM
|
Permanent Service | 10/10/2003 | 10/10/2003 | 10/10/2003 | P | PASS |
Jack Frank
|
|
|
p/s o/h rec. ok
|
Permanent Service | 9/30/2003 | 10/1/2003 | 10/1/2003 | P | FAIL |
Jack Frank
|
|
|
christy-- ###-#### no cor posted did not have access to jbox, needs gutkit, grding all messed up needs #4 to water witin 5 ft, grd rods not 6ft apart, contractor is hunting left message with owner 10/1/2003 3:11:58 PM
|
Permanent Service | 9/19/2003 | 9/19/2003 | 9/19/2003 | P | FAIL |
Mike Kinnear
|
|
|
roger; Phone #: ###-#### Internet Inspection Request from: Annette Moore t/s o/h rec ok t/w electrical contractor he to fix corrections & call for reinspection (d-rating, 2 ground rods, ground within 5ft of water entry, bond hot & cold water pipes, & sunlight resisant wire o/h) they have until 9/29/03 to fix corrections 9/19/2003 1:29:02 PM
|