ELE-Aging Inspection | 12/31/2008 | 12/31/2008 | 1/5/2009 | | FAIL |
Pat Lass
|
|
|
no work done
|
DOC - Permit Expired | 1/5/2009 | 1/5/2009 | 1/5/2009 | P | PASS |
Pat Lass
|
|
|
no work done
|
ELE-Aging Inspection | 10/29/2008 | 10/29/2008 | 10/30/2008 | | NR |
Pat Lass
|
|
|
suc
|
ELE-Aging Inspection | 8/26/2008 | 8/26/2008 | 8/26/2008 | | NR |
Pat Lass
|
|
|
suc
|
Final | 6/23/2008 | 6/25/2008 | 6/25/2008 | A | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 6/23/2008 at 4:39:33 PM. Contact: ###-####. ok to final 812 & 812 1/2, no esc this project
|
Electrical Rough-In | 4/24/2008 | 4/25/2008 | 4/25/2008 | A | PART |
Pat Lass
|
|
|
Dan, apts. #812 & #812 1/2; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok
|
Electrical Rough-In | 4/17/2008 | 4/18/2008 | 4/18/2008 | A | NR |
Jack Frank
|
|
|
Brian, late a.m. if possible ###-#### - apts. 812 & 812 1/2 contr will reschedulefor PM
|
Electrical Rough-In | 4/18/2008 | 4/18/2008 | 4/18/2008 | P | CANC |
Pat Lass
|
|
|
brian note: 812 and 812 1/2 Phone #: ###-####
|
ELE-Aging Inspection | 3/28/2008 | 3/28/2008 | 3/28/2008 | | NR |
Pat Lass
|
|
|
on going project has been done in stages.
|
Final | 1/22/2008 | 1/23/2008 | 1/23/2008 | A | PART |
Pat Lass
|
|
|
dan Note: apt 808 and 808 1/2 please if possible first thing is the morning Phone #: ###-#### 808 and 808 1/2 ok
|
ELE-Aging Inspection | 11/22/2007 | 11/22/2007 | 11/23/2007 | | NR |
Pat Lass
|
|
|
suc
|
Electrical Rough-In | 9/17/2007 | 9/17/2007 | 9/17/2007 | P | PASS |
Bob Reichert
|
|
|
bryan - apt 808 and 801 1/2 Phone #: ###-#### ric ok for units 808 and 808 1/2
|
Electrical Rough-In | 9/13/2007 | 9/13/2007 | 9/13/2007 | P | NR |
Pat Lass
|
|
|
bryan Phone #: ###-####
|
ELE-Aging Inspection | 7/12/2007 | 7/12/2007 | 7/16/2007 | | NR |
Pat Lass
|
|
|
7 units left
|
ELE-Aging Inspection | 4/24/2007 | 4/24/2007 | 4/30/2007 | | NR |
Pat Lass
|
|
|
suc
|
ELE-Aging Inspection | 2/20/2007 | 2/20/2007 | 2/21/2007 | | NR |
Pat Lass
|
|
|
suc
|
ELE-Aging Inspection | 12/6/2006 | 12/6/2006 | 12/12/2006 | | NR |
Pat Lass
|
|
|
suc
|
Final | 10/5/2006 | 10/5/2006 | 10/5/2006 | A | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 10/5/2006 at 7:19:25 AM. Contact: ###-####. partial final on apt 814 and 814-1/2 ok
|
Final | 9/28/2006 | 9/29/2006 | 9/29/2006 | P | NR |
Pat Lass
|
|
|
dan final on apt 814 and 814-1/2; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley still working on it
|
Electrical Rough-In | 8/4/2006 | 8/4/2006 | 8/4/2006 | P | PART |
Pat Lass
|
|
|
derek; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley unit 814 1/2 ok
|
Electrical Rough-In | 8/1/2006 | 8/1/2006 | 8/1/2006 | P | PART |
Pat Lass
|
|
|
amy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles 814 R/I Ok
|
ELE-Aging Inspection | 7/31/2006 | 7/31/2006 | 7/31/2006 | | NR |
Pat Lass
|
|
|
suc
|
Electrical Rough-In | 7/31/2006 | 7/31/2006 | 7/31/2006 | P | CANC |
Pat Lass
|
|
|
derek - ###-#### (cell#) Internet Inspection Request from: Barbara Buckley canceled by sub-contractor
|
ELE-Aging Inspection | 5/29/2006 | 5/29/2006 | 6/1/2006 | | NR |
Pat Lass
|
|
|
suc
|
ELE-Aging Inspection | 3/29/2006 | 3/29/2006 | 3/30/2006 | | NR |
Pat Lass
|
|
|
SUC stoped by job site and talked to contractor
|
ELE-Aging Inspection | 1/23/2006 | 1/23/2006 | 1/23/2006 | | NR |
Pat Lass
|
|
|
suc
|
Electrical Rough-In | 11/18/2005 | 11/18/2005 | 11/18/2005 | P | PASS |
Pat Lass
|
|
|
###-#### - dan Note: apt 816 and 816 1/2 - r/i for cover
|
Rough-In Permanent Service | 9/19/2005 | 9/20/2005 | 9/20/2005 | A | PART |
Pat Lass
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa final ok for 810 and 810.5
|
Rough-In Permanent Service | 9/1/2005 | 9/6/2005 | 9/6/2005 | P | FAIL |
Pat Lass
|
|
|
FINAL ON UNITS 810 AND 810-1/2. UNITS ARE ALL TRIM’D OUT AND READY TO BE INSPECTED ON TUESDAY - PM - THANKS PAT!!; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell 410.8 no open lamps or pendant fixtures in closets no directory in 810
|
Rough-In Permanent Service | 8/31/2005 | 9/2/2005 | 9/1/2005 | A | CANC |
Pat Lass
|
|
|
two units in Jones Apts are ready for a final inspection on Friday morning - Creed or Jason will meet you out back on the alley side of the building on Friday morning. We will call to confirm a time that works for you. Thanks Pat!!; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell Inspection cancelled from web by: Dan Mitchell
|
Rough-In Permanent Service | 7/29/2005 | 8/3/2005 | 8/3/2005 | A | PART |
Pat Lass
|
|
|
###-#### NEED TO FINAL UNIT #917 - IT IS ALL TRIMMED OUT AND ENERGIZED - WE WILL MEET YOU THERE AT 8:30 AM - THANKS!!; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell finaled #917
|
ELE-Aging Inspection | 7/22/2005 | 7/22/2005 | 7/22/2005 | | NR |
Pat Lass
|
|
|
suc
|
Final | 5/13/2005 | 5/17/2005 | 5/17/2005 | P | PART |
Pat Lass
|
|
|
We would like a final inspection on Apartment #917 1/2. Creed (manager) will give you the tour.Thanks!!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell apt 9171/2 ok
|
Electrical Rough-In | 5/3/2005 | 5/4/2005 | 5/4/2005 | A | PART |
Pat Lass
|
|
|
We are ready for a rough-in inspection for apartment #917. Jason will meet you at 8:30 AM. Thanks!!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
|
Electrical Rough-In | 4/28/2005 | 4/29/2005 | 4/29/2005 | A | PART |
Pat Lass
|
|
|
###-#### Ready for a rough-in insp. in one of the apartments. My journeyman will be onsite to give you the tour. Thanks!!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell 4/29/2005 7:50:43 AM
|
Electrical Rough-In | 4/21/2005 | 4/22/2005 | 4/22/2005 | A | PART |
Pat Lass
|
|
|
###-#### We are ready for a rough-in insp. in Apartments #810 & #810 1/2. My Journeyman will be onsite to give you the tour.Thanks!!! Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell 4/22/2005 7:40:18 AM
|
ELE-Aging Inspection | 4/20/2005 | 4/20/2005 | 4/20/2005 | | NR |
Pat Lass
|
|
|
suc 4/20/2005 7:33:04 AM
|
Final | 2/16/2005 | 2/18/2005 | 2/18/2005 | A | PART |
Pat Lass
|
|
|
Please meet us on-site at 8:30 AM to do a final inspection on Apartments #919, and #919 1/2.THANKS!!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
|
Electrical Rough-In | 1/25/2005 | 1/26/2005 | 1/26/2005 | A | PART |
Pat Lass
|
|
|
We are ready for a rough-in inspection in Apt.#919, and Apt.#919 1/2.We will meet you at 8:30 AM to give you the tour. Thanks!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
|
Rough-In Permanent Service | 1/5/2005 | 1/7/2005 | 1/7/2005 | A | PART |
Pat Lass
|
|
|
We are ready for final inspection on Apt.#921, and Apt.#921 1/2.We will leave the permit open for the rest of the apartments.Would you please meet us at 8:30 AM onsite?THANKS!!!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
ok to set meters for both apts
final on both ok 1/7/2005 9:09:01 AM
|
Electrical Rough-In | 12/16/2004 | 12/17/2004 | 12/17/2004 | A | PART |
Pat Lass
|
|
|
Please meet us at 8:30 am to re-inspect.Corrections are made and holes are open.T-H-A-N-K-S !!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
129 &129.5 ok 12/17/2004 8:38:10 AM
|
Final | 12/13/2004 | 12/14/2004 | 12/14/2004 | A | FAIL |
Pat Lass
|
|
|
Ready for rough-in on 2 apartments.Will meet you at 8:30 AM.Thanks!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
found boxes overfilled boxes without connectors and no sheath in the boxes.
must open all pertainent patches on first floor and one in upstairs bath. 12/14/2004 9:20:37 AM
|
Electrical Rough-In | 12/9/2004 | 12/13/2004 | 12/13/2004 | A | NH |
Pat Lass
|
|
|
We are ready to have 2 apartments inspected to allow cover-up.We will meet you on-site @ 8:30 AM to give you the tour.Thanks!!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
open all patched areas for inspection. it is unlawful to cover prior to inspection. 12/13/2004 8:35:32 AM
|
Conference | 12/1/2004 | 12/2/2004 | 12/2/2004 | A | PART |
Pat Lass
|
|
|
Pat, we would like a quick conference with you to clear up a couple of our concerns on this job.Thanks!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
floor receps were discussed 12/2/2004 10:34:28 AM
|
Rough-In Permanent Service | 11/30/2004 | 12/1/2004 | 12/1/2004 | P | PASS |
Pat Lass
|
|
|
###-#### Ready to have the grounding re-inspected.One of my technicians should be onsite.Thanks!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell 12/1/2004 11:45:53 AM
T/S O/H Ok 12/1/2004 2:10:54 PM
|
Temporary Service | 11/24/2004 | 11/26/2004 | 11/26/2004 | A | NR |
William E Thomas
|
|
|
We have had to install a temporary overhead service to tide us over until Idaho Power can provide underground service.(aprox. 30-60 days away).We would like you to inspect this temp. service so Idaho Power will hit it.Thanks!!!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
|
ELE-Aging Inspection | 9/13/2004 | 9/13/2004 | 9/13/2004 | | NR |
Pat Lass
|
|
|
suc 9/13/2004 9:33:13 AM
|
ELE-Aging Inspection | 6/16/2004 | 6/16/2004 | 6/16/2004 | | NR |
Pat Lass
|
|
|
waiting for id power to finish their end op the job 6/18/2004 3:20:39 PM
|
ELE-Aging Inspection | 4/5/2004 | 4/5/2004 | 4/5/2004 | | NR |
Pat Lass
|
|
|
SUC 4/8/2004 4:54:48 PM
|
Rough-In Permanent Service | 1/28/2004 | 1/28/2004 | 1/28/2004 | P | NR |
Pat Lass
|
|
|
Would like to meet at 2:00 today to do a walk-through inspection of this completed phase of the job.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
Had conf 1/28/2004 2:16:40 PM
|
ELE-Aging Inspection | 1/21/2004 | 1/21/2004 | 1/21/2004 | | NR |
Pat Lass
|
|
|
suc 1/22/2004 4:29:06 PM
|
Electrical Rough-In | 9/26/2003 | 9/26/2003 | 9/26/2003 | P | PART |
William E Thomas
|
|
|
Please inspect PVC conduits in trench to allow backfill. Please make this your last job of the day. THANKS !!!!!; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
ok to cover coduit 9/26/2003 2:42:54 PM
|
Electrical Rough-In | 9/23/2003 | 9/24/2003 | 9/24/2003 | P | NR |
Pat Lass
|
|
|
We need the PVC conduits in the trench inspected to allow backfill. Thanks !!!; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
|