Final | 4/7/2004 | 4/7/2004 | 4/7/2004 | P | PASS |
Pat Lass
|
|
|
###-#### glenn
|
Final | 4/1/2004 | 4/2/2004 | 4/2/2004 | A | FAIL |
Pat Lass
|
|
|
glen; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
hood fan lights not wired properly 4/2/2004 11:27:40 AM
|
Final | 3/23/2004 | 3/24/2004 | 3/24/2004 | A | NR |
Mike Kinnear
|
|
|
glenn; Phone #: ###-#### Internet Inspection Request from: Barbara Moore correction made in house. range hood not installed 3/24/2004 8:43:48 AM
|
Final | 3/23/2004 | 3/23/2004 | 3/23/2004 | P | FAIL |
Pat Lass
|
|
|
glenn; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
install kitchen counter recep. and take juice bar receps off bathroom circuit 3/23/2004 3:07:53 PM
|
Electrical Rough-In | 1/27/2004 | 1/28/2004 | 1/28/2004 | A | PASS |
Pat Lass
|
|
|
glenn; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
Electrical Rough-In | 1/20/2004 | 1/20/2004 | 1/20/2004 | P | FAIL |
Jack Frank
|
|
|
single car garage- glenn ###-#### cor. posted called 210.11 (C)(3), 314.16 box fill 2 gang garage entry ., proper feed fo electric furnace upstair #8 not correct amps too small 1/20/2004 3:26:20 PM
|
Rough-In Permanent Service | 10/1/2003 | 10/2/2003 | 10/2/2003 | A | PART |
Mike Kinnear
|
|
|
###-#### darin ok cover part ri garage not done. survey outlet wall spacing & counter top spacing. p/s u/g n ok survey ground wire can not pass thru service panal called contractor & advised 10/2/2003 10:38:43 AM
|
Rough-In Permanent Service | 9/30/2003 | 10/1/2003 | 10/1/2003 | P | FAIL |
Mike Kinnear
|
|
|
glenn ###-#### no approved set prints on job site 10/1/2003 4:43:34 PM
|
Rough-In Permanent Service | 9/30/2003 | 9/30/2003 | 9/30/2003 | P | CANC |
Pat Lass
|
|
|
###-#### glenn--cancel per glenn
|