Final | 4/28/2004 | 4/29/2004 | 4/29/2004 | A | PASS |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 4/28/2004 at 4:07:32 PM. Contact: ###-####. or ###-#### allen
final ok 4/29/2004 11:33:18 AM
|
Final | 2/11/2004 | 2/11/2004 | 2/11/2004 | P | FAIL |
Jack Frank
|
|
|
ED; Phone #: ###-#### Internet Inspection Request from: Darla Downs cor. posted called 110.3(B) manufactures breakers only, 110.26 clearence for p/s, remove phone equip. from below and required clearence for sub panel, 250 p/s and sub panel, ged and bond to p/s, address what was p/s as sub panel addess range and dryer feeds, 220 calculate service for proper size 2/11/2004 2:37:30 PM
|