Final | 12/16/2003 | 12/16/2003 | 12/16/2003 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 12/16/2003 at 11:25:05 AM. Contact: ###-####.ok
12/16/2003 2:09:50 PM
|
Final | 12/4/2003 | 12/4/2003 | 12/4/2003 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 12/4/2003 at 7:36:46 AM. Contact: ###-####. cor. posted called 110.26 (F)(1)a clearence for panel remove shelf from floor up, 312.3 panel shall be flush with combustible finish, 250.4 (A)(4) grd plug mold at splice box, 250.6(A) plug mold shorted out, and gfci at island counter bad 12/4/2003 1:53:55 PM
|
Final | 12/1/2003 | 12/2/2003 | 12/2/2003 | A | PART |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 12/1/2003 at 5:18:47 PM. Contact: ###-####.
temp occup. ok
support existing flex and low voltage wires in drop cieling 12/2/2003 3:31:10 PM
|
Electrical Rough-In | 11/10/2003 | 11/12/2003 | 11/12/2003 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 11/10/2003 at 11:05:40 AM. Contact: ###-####. u/g and walls 11/12/2003 10:34:34 AM
|
Electrical Rough-In | 11/10/2003 | 11/10/2003 | 11/10/2003 | P | CANC |
Jack Frank
|
|
|
for trench insp-steve; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Disp set to [CANC] by a contractor via Hello! on Nov 10 2003 11:03AM.
|