Final | 7/26/2004 | 7/26/2004 | 7/26/2004 | P | PASS |
Pat Lass
|
|
|
Jerry; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
Final | 7/22/2004 | 7/23/2004 | 7/23/2004 | A | FAIL |
Pat Lass
|
|
|
jerry; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
GFCI protect Hydro tub
clear space about equipment in garage and 210.52 in kitchen 7/23/2004 11:27:13 AM
|
Final | 7/20/2004 | 7/21/2004 | 7/21/2004 | P | CANC |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 7/20/2004 at 4:26:49 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jul 21 2004 8:52AM.
|
Final | 7/16/2004 | 7/19/2004 | 7/19/2004 | A | CANC |
Pat Lass
|
|
|
jerry; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles - canc 8:11 7/19/2004 - am - will rescheduled - cmc
|
Electrical Rough-In | 11/24/2003 | 11/24/2003 | 11/24/2003 | P | PASS |
William E Thomas
|
|
|
rough ok, survey nec 210.52 recep spacing
|
Final | 11/24/2003 | 11/24/2003 | 11/24/2003 | P | CANC |
William E Thomas
|
|
|
Kevine; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
wrong inspection 11/24/2003 3:34:04 PM
|
Electrical Rough-In | 11/19/2003 | 11/19/2003 | 11/19/2003 | P | FAIL |
William E Thomas
|
|
|
###-#### Kevin --- please call for access. thanks.
nec 210.52 spacing, 334.30 supporting & securing, 300.4 protection from physical damage. 11/19/2003 4:34:21 PM
|