Permit Information
Permit NumberELE03-03871
StatusFinaled
Name ACE ELECTRIC ST LIC # C-29248
Site Address 1780 S DOE CREEK WAY
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/11/20043/11/20043/11/2004PPASS
DetailsJack Frank
TRAVIS; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok 3/11/2004 3:16:28 PM
Final3/10/20043/10/20043/10/2004PFAIL
DetailsJack Frank
travis; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. posted called needs access to jtub, needs shade or guard for fixture in storage off of N E bedrm 410.5 3/10/2004 1:43:11 PM
Permanent Service1/20/20041/21/20041/21/2004APASS
DetailsMike Kinnear
Ray; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
p/s u/g n ok 1/21/2004 10:18:12 AM
Electrical Rough-In1/8/20041/9/20041/9/2004APASS
DetailsMike Kinnear
ok to cover- ace ele; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok cover ri survey 210.52(A)&(B) outlet wall spacing & counter top spacing 1/9/2004 12:06:43 PM
Conference1/6/20041/6/20041/6/2004PPART
DetailsJack Frank
TRAVIS ; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok met with Jim S and contractor 1/6/2004 1:35:30 PM
Electrical Rough-In1/5/20041/5/20041/5/2004PFAIL
DetailsJack Frank
ray; Phone #: ###-#### Internet Inspection Request from: Annette Moore cor. posted called 314.16, 250.148 splice all equip grds at boxes, 210.52(A)&(B) outlet wall, and countertop spacing, 300.14 wires way too short grds at boxes, 404.8 breakers higher than 6ft 7inches 1/5/2004 3:34:58 PM