Final | 3/11/2004 | 3/11/2004 | 3/11/2004 | P | PASS |
Jack Frank
|
|
|
TRAVIS; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok 3/11/2004 3:16:28 PM
|
Final | 3/10/2004 | 3/10/2004 | 3/10/2004 | P | FAIL |
Jack Frank
|
|
|
travis; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. posted called needs access to jtub, needs shade or guard for fixture in storage off of N E bedrm 410.5 3/10/2004 1:43:11 PM
|
Permanent Service | 1/20/2004 | 1/21/2004 | 1/21/2004 | A | PASS |
Mike Kinnear
|
|
|
Ray; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
p/s u/g n ok 1/21/2004 10:18:12 AM
|
Electrical Rough-In | 1/8/2004 | 1/9/2004 | 1/9/2004 | A | PASS |
Mike Kinnear
|
|
|
ok to cover- ace ele; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok cover ri survey 210.52(A)&(B) outlet wall spacing & counter top spacing 1/9/2004 12:06:43 PM
|
Conference | 1/6/2004 | 1/6/2004 | 1/6/2004 | P | PART |
Jack Frank
|
|
|
TRAVIS ; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok met with Jim S and contractor 1/6/2004 1:35:30 PM
|
Electrical Rough-In | 1/5/2004 | 1/5/2004 | 1/5/2004 | P | FAIL |
Jack Frank
|
|
|
ray; Phone #: ###-#### Internet Inspection Request from: Annette Moore cor. posted called 314.16, 250.148 splice all equip grds at boxes, 210.52(A)&(B) outlet wall, and countertop spacing, 300.14 wires way too short grds at boxes, 404.8 breakers higher than 6ft 7inches 1/5/2004 3:34:58 PM
|