Final | 3/11/2004 | 3/12/2004 | 3/12/2004 | A | PASS |
Jack Frank
|
|
|
after 10 please///josh or jim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok 3/12/2004 12:24:57 PM
|
Electrical Rough-In | 1/23/2004 | 1/23/2004 | 1/23/2004 | P | PASS |
Jack Frank
|
|
|
James -- anytime after 2:00 please if possible, thanks.; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes ok 1/23/2004 3:30:06 PM
|
Electrical Rough-In | 1/20/2004 | 1/21/2004 | 1/21/2004 | P | FAIL |
Jack Frank
|
|
|
call 1st before insp jim- ###-#### cor. posted met owner 300.4, 210.52(A) , 250 148, 334.30&314.17(A), 300.14, 110.12(A), 314.17, replace 2&3 gang boxes with broken clamps, 352.30 (A), 310.15(B) derate for over 10 wires in conduit, 250.22(B) proper size equip grd for deration, 110.3(B)& BCC no violations retained for breakers non GE and owner work done without permit 3 years ago in old part of house "COW" do not cover posted 1/21/2004 2:23:34 PM
|
Electrical Rough-In | 1/14/2004 | 1/15/2004 | 1/15/2004 | A | FAIL |
Jack Frank
|
|
|
James ###-#### --- would like after 10:30 if possible please. thanks. no r/i conference only owner needs plans stating what rooms are and where counters will be, and needs to study up on basic house wiring job not ready and many violations 1/15/2004 12:50:09 PM
|