Final | 6/1/2004 | 6/1/2004 | 6/1/2004 | P | PASS |
Mike Kinnear
|
|
|
Joe; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes ok final 6/1/2004 2:37:23 PM
|
Final | 5/27/2004 | 5/28/2004 | 5/27/2004 | A | CANC |
Mike Kinnear
|
|
|
Joe; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes--cancel per joe will re-schedule
|
Final | 5/26/2004 | 5/26/2004 | 5/26/2004 | P | FAIL |
Jack Frank
|
|
|
joe; Phone #: ###-#### Internet Inspection Request from: Barbara Moore NR and partial cor posted reversed polarity , 410.8 for closet and install shelves and rods, gfci for outlets within6ft of wet bar sink, remove range from kit circuit called 5/26/2004 2:47:20 PM
|
Rough-In Permanent Service | 2/1/2004 | 2/2/2004 | 2/2/2004 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 2/1/2004 at 11:00:40 AM. r/i ok
p/s u/g new ok 2/2/2004 9:11:31 AM
|
Rough-In Permanent Service | 1/29/2004 | 1/30/2004 | 1/30/2004 | A | FAIL |
Jack Frank
|
|
|
Joe; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes cor. posted called 314.16 box fill everywhere, 300.4 nail plates and 11/4" 422.15 and 210.23(A) needs #12 for vacuum outlet on 20 amp circuits and vacuum outlets not allowed on kit. circuit, replace damaged 12/2 romex stairs landing garage wall 1/30/2004 11:31:47 AM
|