Permit Information
Permit NumberELE04-00146
StatusFinaled
Name E-ZEE ELECTRIC
Site Address 121 E HIGHLAND ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/1/20046/1/20046/1/2004PPASS
DetailsMike Kinnear
Joe; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes ok final 6/1/2004 2:37:23 PM
Final5/27/20045/28/20045/27/2004ACANC
DetailsMike Kinnear
Joe; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes--cancel per joe will re-schedule
Final5/26/20045/26/20045/26/2004PFAIL
DetailsJack Frank
joe; Phone #: ###-#### Internet Inspection Request from: Barbara Moore NR and partial cor posted reversed polarity , 410.8 for closet and install shelves and rods, gfci for outlets within6ft of wet bar sink, remove range from kit circuit called 5/26/2004 2:47:20 PM
Rough-In Permanent Service2/1/20042/2/20042/2/2004APASS
DetailsJack Frank
Scheduled by a contractor via Hello! on 2/1/2004 at 11:00:40 AM. r/i ok
p/s u/g new ok 2/2/2004 9:11:31 AM
Rough-In Permanent Service1/29/20041/30/20041/30/2004AFAIL
DetailsJack Frank
Joe; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes cor. posted called 314.16 box fill everywhere, 300.4 nail plates and 11/4" 422.15 and 210.23(A) needs #12 for vacuum outlet on 20 amp circuits and vacuum outlets not allowed on kit. circuit, replace damaged 12/2 romex stairs landing garage wall 1/30/2004 11:31:47 AM