DOC - Permit Expired | 10/14/2008 | 10/14/2008 | 10/14/2008 | P | PASS |
Jack Frank
|
|
|
|
Electrical Rough-In | 2/12/2008 | 2/13/2008 | 2/13/2008 | A | PASS |
Bob Reichert
|
|
|
john Phone #: ###-#### corrections made, ok to cover walls only, will have contractor do service later
|
Electrical Rough-In | 12/10/2007 | 12/14/2007 | 12/14/2007 | A | FAIL |
Bob Reichert
|
|
|
John Please call 15 min before going out Phone #: ###-#### met owner, left correction notice, BCC all make-up shall be done, NEC 210.70(A)(2)(c) shall provide switch for lighting at top of stairs-to control from top or bottom (3-way), 314.17(C) shall staple nm cable within 8" of box
|
DOC - Permit Expired | 11/21/2007 | 11/21/2007 | 11/21/2007 | P | PASS |
Jack Frank
|
|
|
|