Electrical Rough-In | 4/21/2004 | 4/22/2004 | 4/22/2004 | P | PASS |
Jack Frank
|
|
|
###-#### marshal
|
Electrical Rough-In | 4/22/2004 | 4/22/2004 | 4/22/2004 | P | CANC |
Jack Frank
|
|
|
marshall; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
Final | 4/22/2004 | 4/22/2004 | 4/22/2004 | P | PASS |
Jack Frank
|
|
|
ok
|
Permanent Service | 4/22/2004 | 4/22/2004 | 4/22/2004 | P | PASS |
Jack Frank
|
|
|
p/s o/h rec. ok
|
Electrical Rough-In | 3/18/2004 | 3/19/2004 | 3/19/2004 | A | FAIL |
Jack Frank
|
|
|
call 1st before insp-- ###-####- or ###-####- bart cor. posted called needs 2 grd rods, grd or bond water system shall not use #12 white as phase conductor, needs new box for dyer recept, clean paint off pipe at grd clamp, do not double 2 circuits on 1 breaker , address neutral to phase load 3/19/2004 9:01:07 AM
|
Electrical Rough-In | 3/15/2004 | 3/15/2004 | 3/15/2004 | P | NH |
Jack Frank
|
|
|
###-#### bart notice posted called left number message 3/15/2004 3:12:12 PM
|