Final | 2/10/2004 | 2/10/2004 | 2/10/2004 | P | PASS |
Jack Frank
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Annette Moore called shall use manufactures listed breakers only
p/s o/h rec. ok 2/10/2004 12:25:21 PM
|
Permanent Service | 2/6/2004 | 2/6/2004 | 2/6/2004 | P | FAIL |
Jack Frank
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Annette Moore no cor. posted electrician angry and left job called contractor met with Dan K of Power PLus and resloved problems contractor will reschedule inspection when corrections made GEC shall be at p/s not sub panel, shall not pass GEC in feeder raceway to sub panel and pass through sub panel shall remove feeder to sub panel from mwtwer enclousure,, shall not ID #6 or smaller equip grd 2/6/2004 3:52:36 PM
|
Permanent Service | 2/5/2004 | 2/5/2004 | 2/5/2004 | P | NR |
Jack Frank
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|