Final | 10/28/2004 | 10/29/2004 | 10/29/2004 | A | PASS |
William E Thomas
|
|
|
mike-call before you go out; Phone #: ###-#### Internet Inspection Request from: Jan Rice
|
Final | 10/27/2004 | 10/27/2004 | 10/27/2004 | P | FAIL |
Jack Frank
|
|
|
mike please call before you go; Phone #: ###-#### Internet Inspection Request from: Jan Rice cor. 314.28 straight thur pull with splices needs box 6 x the diameter 2 locations water heaters, bond bushing for RE washers, 240.21 needs over current protection secondary side x formers taps over 25ft 10/27/2004 3:17:50 PM
|
ELE-Aging Inspection | 10/4/2004 | 10/4/2004 | 10/4/2004 | | NR |
Pat Lass
|
|
|
suc 10/6/2004 1:39:37 PM
|
ELE-Aging Inspection | 8/2/2004 | 8/2/2004 | 8/2/2004 | | NR |
Pat Lass
|
|
|
|
Electrical Rough-In | 5/24/2004 | 5/24/2004 | 5/24/2004 | P | PART |
Pat Lass
|
|
|
###-####. Scheduled by a contractor via Hello! on 5/24/2004 at 8:38:49 AM. Contact: ###-####. 5/24/2004 11:31:44 AM
ANOP 5/24/2004 2:36:10 PM
|
ELE-Aging Inspection | 5/10/2004 | 5/10/2004 | 5/10/2004 | | NR |
Pat Lass
|
|
|
SUC 5/14/2004 11:32:41 AM
|