Final | 4/20/2004 | 4/21/2004 | 4/21/2004 | A | PASS |
Mike Kinnear
|
|
|
Ron; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes ok final 4/21/2004 9:38:57 AM
|
Final | 4/15/2004 | 4/16/2004 | 4/16/2004 | A | FAIL |
Mike Kinnear
|
|
|
ron; Phone #: ###-#### Internet Inspection Request from: Darla Downs called contractor correction NEC210.52(C)(1) shall have duplex receptacle in 2ft wall space not in cabinets in all units note conduit & wire to out building shall be removed or bring up theNEC 4/16/2004 9:24:18 AM
|
Rough-In Permanent Service | 2/11/2004 | 2/12/2004 | 2/12/2004 | A | NH |
Mike Kinnear
|
|
|
RON; Phone #: ###-#### Internet Inspection Request from: Darla Downs no access called 2/12/2004 9:12:08 AM
|
Rough-In Permanent Service | 2/12/2004 | 2/12/2004 | 2/12/2004 | P | PASS |
Mike Kinnear
|
|
|
ron; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok cover ri
p/s u/g n ok
2/12/2004 3:32:56 PM
|
Rough-In Permanent Service | 2/10/2004 | 2/10/2004 | 2/10/2004 | P | FAIL |
Jack Frank
|
|
|
ron- ###-#### cor. posted called 210.52(B) range hood or micro wave on kit circuit, 314.43, 314.16, 314.20, 110.12(A) replace plastic boxes with unused KOs, 110.3(B) shall install all factory parts neutral buses in sub panels and install eqiup grd kit for grd wires, 210.52(A) add reguired outlets and outlet spacing, 210.52(), and 210.11(C)(2), owner job taken over by Spencer electric 2/10/2004 2:48:53 PM
|