Temporary Service | 2/2/2005 | 2/3/2005 | 2/3/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 2/2/2005 at 1:48:32 PM. Contact: ###-####. corrections made. t/s o/h n ok 2/3/2005 9:22:01 AM
|
Temporary Service | 2/1/2005 | 2/2/2005 | 2/2/2005 | A | FAIL |
Bob Reichert
|
|
|
###-#### larry 110.12(A) unused openings shall be closed, 110.3, Fittings shall be listed for the purpose, 404.7 Breaker handle in up position shall be on not off. 2/2/2005 10:11:47 AM
|
Temporary Service | 2/26/2004 | 2/26/2004 | 2/26/2004 | P | PASS |
Joe Ray
|
|
|
danny; Phone #: ###-#### Internet Inspection Request from: Barbara Moore t/s oh n ok 2/26/2004 5:47:42 PM
|
Temporary Service | 2/24/2004 | 2/24/2004 | 2/24/2004 | P | FAIL |
Joe Ray
|
|
|
mark ; Phone #: ###-#### Internet Inspection Request from: Annette Moore support box/flex ----- inuse covers-------protection of flex from physical damage 2/24/2004 1:57:32 PM
|