Final | 4/14/2004 | 4/14/2004 | 4/14/2004 | A | PASS |
Jack Frank
|
|
|
final occupancy ok
|
Permanent Service | 4/14/2004 | 4/14/2004 | 4/14/2004 | P | PASS |
Jack Frank
|
|
|
brad; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
p/s o/h rec. ok 4/14/2004 11:43:25 AM
|
Final | 4/13/2004 | 4/13/2004 | 4/13/2004 | P | PART |
Jack Frank
|
|
|
BRAD; Phone #: ###-#### Internet Inspection Request from: Darla Downs THIS WILL ALSO NEED TO HAVE THE SERVICE CHECKED PER JACK FRANK ///DLD
T/O ok only 4/13/2004 1:16:34 PM
|
Permanent Service | 4/13/2004 | 4/13/2004 | 4/13/2004 | P | FAIL |
Jack Frank
|
|
|
THIS ALSO NEED THE SERVICE CHECKED ///DLD cor. posted called left message 250.8 no SMS for grds or bonds, 110.3(B) use manufactures bond screw at p/s, 110.15 ID high leg orange, 200.6 ID neutral white , gray , or other approved means 4/13/2004 1:21:13 PM
|
Final | 4/8/2004 | 4/9/2004 | 4/9/2004 | A | FAIL |
Jack Frank
|
|
|
brad; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie cor. posted called 110.12(A) seal all unused openings boxes , fixtures , panels 410.14 (B) make sure fixtures mounted to boxes have aacess holes cut , so box is accessible,, 110.3(B) manufactures listed breakers only, BCC 4-05-10 no violations to be retained 4/9/2004 9:42:16 AM
|
Electrical Rough-In | 3/19/2004 | 3/22/2004 | 3/22/2004 | A | PART |
Jack Frank
|
|
|
OFFICE; Phone #: 9###-#### Internet Inspection Request from: Darla Downs
walls ok 3/22/2004 8:22:17 AM
|