Final | 4/30/2004 | 4/30/2004 | 4/30/2004 | P | PASS |
Mike Kinnear
|
|
|
NEED FINAL INSPECTION; Phone #: ###-#### Internet Inspection Request from: Dawn Moore ok final 4/30/2004 3:50:23 PM
|
Final | 4/6/2004 | 4/7/2004 | 4/7/2004 | A | CANC |
Mike Kinnear
|
|
|
Internet Inspection Request from: Dawn Moore
|
Permanent Service | 4/6/2004 | 4/7/2004 | 4/7/2004 | A | PASS |
Pat Lass
|
|
|
###-#### Andrea Price
P/S O/H R Ok 4/7/2004 9:38:52 AM
|
Permanent Service | 4/5/2004 | 4/6/2004 | 4/6/2004 | A | FAIL |
Jack Frank
|
|
|
jack ###-#### 31205(C) exception conduit with ser cable in it, 110.26(F)(2) remove phone and T V from below p/s 250.53,54,56 install 2 grd rods called 4/6/2004 8:58:00 AM
|
Electrical Rough-In | 3/26/2004 | 3/26/2004 | 3/26/2004 | P | PASS |
Mike Kinnear
|
|
|
ok cover ri survey nec210.52 kit. counter next to range & 6 ft. back kit. wall in all 4 units.
|
Rough-In Permanent Service | 3/25/2004 | 3/26/2004 | 3/26/2004 | P | CANC |
Mike Kinnear
|
|
|
early afternoon please. 4 plex rough-in and permenant service; Phone #: ###-#### Internet Inspection Request from: Dawn Moore wrong type inspection 3/26/2004 2:22:24 PM
|