Final | 6/16/2004 | 6/16/2004 | 6/16/2004 | P | PASS |
Jim Schmer
|
|
|
Scheduled by a contractor via Hello! on 6/16/2004 at 10:14:00 AM. Contact: ###-####.
|
Final | 5/19/2004 | 5/20/2004 | 5/20/2004 | A | FAIL |
Pat Lass
|
|
|
final: Sign listing on power pole; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen
numbers don't match 5/20/2004 11:20:34 AM
|
Final | 4/29/2004 | 4/30/2004 | 4/30/2004 | A | PART |
Pat Lass
|
|
|
T/O is ok
all we need is listing info on ploes by checkouts 4/30/2004 9:11:14 AM
|
Final | 4/28/2004 | 4/29/2004 | 4/29/2004 | A | PART |
William E Thomas
|
|
|
tobi; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
needs panel schedule, and ul numbers for power poles. 4/29/2004 10:06:00 AM
|
Final | 4/29/2004 | 4/29/2004 | 4/29/2004 | P | CANC |
Pat Lass
|
|
|
toby; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
not ready 4/29/2004 12:36:58 PM
|
Final | 4/27/2004 | 4/29/2004 | 4/29/2004 | A | CANC |
Jim Schmer
|
|
|
Scheduled by a contractor via Hello! on 4/27/2004 at 11:46:48 AM. Contact: ###-####. cancel, had two called in. JMS 4/28/2004 4:45:27 PM
|
Final | 4/28/2004 | 4/28/2004 | 4/28/2004 | P | FAIL |
Pat Lass
|
|
|
toby; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
no show window receps.
check all wiring in outside displays boxes and mc cable not supported and sheetmetal screws used for grounding.
250.148 on wireway above panels.
check listing on multi outlet assemblly if it was listed with a switched light on it.
4/28/2004 3:31:13 PM
|
Electrical Rough-In | 4/19/2004 | 4/20/2004 | 4/20/2004 | P | PART |
Jim Schmer
|
|
|
Ceiling oover inspection contact Toby on site; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen ceiling ok except above cashier stands and office (sw corner). 4/20/2004 1:02:50 PM
|
Electrical Rough-In | 3/25/2004 | 3/26/2004 | 3/26/2004 | P | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 3/25/2004 at 2:47:24 PM. Contact: ###-####.
wall R/I Ok 3/26/2004 3:53:35 PM
|
Final | 6/7/2004 | 6/7/2004 | | | |
Jim Schmer
|
|
|
11 am meeting on signs (power poles)
|