Final | 11/3/2004 | 11/4/2004 | 11/4/2004 | A | NR |
Bob Reichert
|
|
|
justin; Phone #: ###-#### Internet Inspection Request from: Barbara Moore not ready, conference w/ elect will recall 11/4/2004 9:24:11 AM
|
Final | 11/4/2004 | 11/4/2004 | 11/4/2004 | P | PASS |
Jack Frank
|
|
|
Justine-Reinspection; Phone #: ###-#### Internet Inspection Request from: Cheryl Baumgartner ok 11/4/2004 1:45:35 PM
|
Permanent Service | 10/11/2004 | 10/12/2004 | 10/12/2004 | A | PASS |
Jack Frank
|
|
|
justin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s o/h rec ok 10/11/2004 2:37:54 PM
|
Rough-In Permanent Service | 10/6/2004 | 10/7/2004 | 10/7/2004 | A | FAIL |
Jack Frank
|
|
|
###-#### brian called needs guy kit, and bonding type meyers hub 10/7/2004 10:30:57 AM
|
Electrical Rough-In | 9/3/2004 | 9/7/2004 | 9/7/2004 | A | PASS |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 9/3/2004 at 12:52:46 PM. Contact: ###-####.
|
Electrical Rough-In | 9/2/2004 | 9/2/2004 | 9/2/2004 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 9/2/2004 at 7:58:45 AM. Contact: ###-####. called still needs to correct box fill , grd metal boxes , 9/2/2004 11:42:18 AM
|
Electrical Rough-In | 8/26/2004 | 8/27/2004 | 8/27/2004 | A | FAIL |
Jack Frank
|
|
|
brian; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles cor. posted called 300.4 314.16, 314.43,314.20, 314.17 broken clamps in 2,3 gang boxes, 314.23 boxes just set in plaster not secure to anything 210.52 (C) needs outlet 12" counter left of range, 250.148 also fee due 8/27/2004 10:25:04 AM
|
Electrical Rough-In | 8/19/2004 | 8/19/2004 | 8/19/2004 | P | FAIL |
Jack Frank
|
|
|
lisa; Phone #: ###-#### Internet Inspection Request from: Annette Moore cor. posted called left message,300.4, 314.16, 314.20, 314.14 replace 2,3 gang boxes with internal clamps broken out, 314.43 no screws or nails allowed in nonmetallic boxes,404.4 remove switch from tub, shower space, BCC no violation to be retained, needs approved plans on job site 8/19/2004 2:47:12 PM
|
Electrical Rough-In | 7/13/2004 | 7/14/2004 | 7/14/2004 | A | FAIL |
Jim Schmer
|
|
|
justin; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok cover ri note survey wall spacing in upstairs kit 7/14/2004 9:25:29 AM Stop work posted, work being done over and above BLD permit. also 10 rooms short. 7/15/2004 10:31:11 AM
|
Electrical Rough-In | 7/13/2004 | 7/14/2004 | 7/14/2004 | A | FAIL |
Mike Kinnear
|
|
|
justin; Phone #: ###-#### Internet Inspection Request from: Annette Moore failed do not cover per 324 & transfered inspection to 324 7/14/2004 2:25:08 PM
|
Final | 7/9/2004 | 7/12/2004 | 7/12/2004 | P | CANC |
William E Thomas
|
|
|
lisa; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
wrong type inspection 7/12/2004 3:15:53 PM
|
Rough-In Permanent Service | 7/12/2004 | 7/12/2004 | 7/12/2004 | P | FAIL |
William E Thomas
|
|
|
250.52 grounding of water pipe, 334.30, 314.4, 314.17, notice posted
|
Temporary Service | 7/12/2004 | 7/12/2004 | 7/12/2004 | P | PASS |
William E Thomas
|
|
|
t/s o/h n ok
|