Final | 7/9/2004 | 7/9/2004 | 7/9/2004 | P | PASS |
William E Thomas
|
|
|
Jack, your requested corrections have been completed. The Customer requests the inspection be AFTER 2 PM. Thanks!!! Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
|
Rough-In Permanent Service | 6/7/2004 | 6/10/2004 | 6/10/2004 | A | FAIL |
Jack Frank
|
|
|
We hard-wired his sprinkler clock into an existing receptacle in the dining room. Customer requests that you give them a 20 minute heads-up call before you arrive:###-####. Thanks!!! Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell cor. posted called 314.3 shall install bond bushing ,or use non metallic conduit at time clock, 314.16 box fill (old box), 210.19 shall not use #14 to tap form #12(pig tial to recept) 250.148 is box grounded ? (old box) 6/10/2004 9:59:18 AM
|
Rough-In Permanent Service | 6/2/2004 | 6/3/2004 | 6/2/2004 | P | CANC |
Jack Frank
|
|
|
We installed a new 20 amp 120 volt circuit and receptacle for a new copier.Thanks!!! Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell Inspection cancelled from web by: Dan Mitchell
|