Final | 6/21/2004 | 6/21/2004 | 6/21/2004 | A | PASS |
Jack Frank
|
|
|
Dan- door open; Phone #: ###-#### Internet Inspection Request from: Dan Hobdey ok 6/21/2004 9:01:24 AM
|
Final | 6/18/2004 | 6/18/2004 | 6/18/2004 | P | CANC |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/18/2004 at 7:45:38 AM. Contact: ###-####. Inspection cancelled from web by: Cathy Chiles
|
Final | 6/17/2004 | 6/17/2004 | 6/17/2004 | P | FAIL |
Jack Frank
|
|
|
dan; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles cor. not made 300.4 needs 11/4 inches for romex called left message 6/17/2004 1:05:26 PM
|
Final | 6/7/2004 | 6/7/2004 | 6/7/2004 | P | FAIL |
Jack Frank
|
|
|
call 1st for access dan ###-#### cor. posted called 334.15 (B) protect romex, 250.8 no SMS allowed for grd or bond lug on siding, 410.30(C) outlet shall be directly above fixture, 400.8 shall not tiewrap cord to anything also needs power 6/7/2004 2:53:22 PM
|
Permanent Service | 6/7/2004 | 6/7/2004 | 6/7/2004 | P | PASS |
Jack Frank
|
|
|
dan-- ###-####--call 1st for access
p/s o/h new ok 6/7/2004 2:50:06 PM
|