ELE-Aging Inspection | 4/20/2005 | 4/20/2005 | 4/20/2005 | | DONE |
Jack Frank
|
|
|
corrections made this was finaled already 4/21/2005 9:02:08 AM
|
Permanent Service | 6/18/2004 | 6/18/2004 | 6/18/2004 | A | PASS |
Jack Frank
|
|
|
p/s u/g new ok
|
Rough-In Permanent Service | 6/18/2004 | 6/18/2004 | 6/18/2004 | A | FAIL |
Jack Frank
|
|
|
see added p/s r/i fail cor. posted called left message 250.148 box in vault, 310.15 (B)(2) derate wires in conduit from p/s to vault 6/18/2004 9:43:43 AM
|
Final | 6/17/2004 | 6/17/2004 | 6/17/2004 | P | FAIL |
Jack Frank
|
|
|
jamie; Phone #: ###-#### Internet Inspection Request from: Annette Moore p/s not listed as service equip. 6/17/2004 12:33:27 PM
|
Final | 6/16/2004 | 6/16/2004 | 6/16/2004 | P | FAIL |
Mike Kinnear
|
|
|
jaimee; Phone #: ###-#### Internet Inspection Request from: Annette Moore UL listing & lable -- called contractor they need to uncover ground rods. 6/16/2004 2:17:15 PM
|
Final | 6/10/2004 | 6/11/2004 | 6/11/2004 | A | NR |
Pat Lass
|
|
|
Bonnie; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
not enough info to write a correction.
no R/I inspection called for. vault not finished.
did not see grounding electrodes or u/g installations. could not find listing on pedistal.
called contractor got mach. left message. 6/11/2004 10:47:34 AM
|