Final | 8/18/2004 | 8/19/2004 | 8/19/2004 | A | PASS |
William E Thomas
|
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
Final | 8/16/2004 | 8/16/2004 | 8/16/2004 | P | CANC |
Mike Kinnear
|
|
|
jim ###-####
|
Permanent Service | 8/2/2004 | 8/2/2004 | 8/2/2004 | P | PASS |
Jack Frank
|
|
|
p/s o/h new ok
|
Electrical Rough-In | 6/24/2004 | 6/24/2004 | 6/24/2004 | P | PASS |
Mike Kinnear
|
|
|
also underground--jim; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok cover ri house & garage ok cover under ground conduit note survey wall spacing kit counter outlets 6/24/2004 2:52:26 PM 6/24/2004 2:54:06 PM
|
Permanent Service | 6/23/2004 | 6/23/2004 | 6/23/2004 | A | PASS |
Jack Frank
|
|
|
p/s o/h new ok
|
Rough-In Permanent Service | 6/22/2004 | 6/23/2004 | 6/23/2004 | A | FAIL |
Jack Frank
|
|
|
JIM; Phone #: ###-#### Internet Inspection Request from: Annette Moore see added p/s
all corrections not made 6" free conductor and make up not complete called 6/23/2004 8:05:01 AM
|
Electrical Rough-In | 6/22/2004 | 6/22/2004 | 6/22/2004 | P | FAIL |
Jack Frank
|
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles met contractor 300.14 short conductors, 314.16 box fill 300.4 11/4", remove range hood from kit circuit, provide access too GEC acorn clamp from outside, not under house
do not cover 6/22/2004 1:54:09 PM
|