Final | 10/4/2004 | 10/4/2004 | 10/4/2004 | P | PASS |
Jack Frank
|
|
|
CONTACT: JON STARKE; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok no card at job site 10/4/2004 1:17:06 PM
|
Final | 9/30/2004 | 10/1/2004 | 10/1/2004 | A | FAIL |
Jack Frank
|
|
|
jon strake ###-#### 9/30/2004 4:13:01 PM cor. posted met contractor needs to bond to sprinkler system ,use GE brackers only, 410.14 hole in fixture too access box, use manufactures boxes and fittings for plugmold, to maintain electrical and mechanical continuity from box to plugmold, use makers listed neutral bus at p/s 10/1/2004 9:56:38 AM
|
Final | 9/30/2004 | 9/30/2004 | 9/30/2004 | P | CANC |
Jack Frank
|
|
|
CONTACT: JON STARKE; Phone #: ###-#### Internet Inspection Request from: Deb McCoy called left message need to meet with contractor 9/30/2004 4:11:03 PM
|
Electrical Rough-In | 8/12/2004 | 8/13/2004 | 8/13/2004 | P | PASS |
Jack Frank
|
|
|
CONTACT: JON STARKE; Phone #: ###-#### Internet Inspection Request from: Deb McCoy r/i ok, needs main disconnect service entrance conductors shall be outside , and grd to watersystem and 2 grd rods called 8/13/2004 3:34:53 PM
|