Final | 1/5/2005 | 1/5/2005 | 1/5/2005 | P | PASS |
Bob Reichert
|
|
|
Terry; Phone #: ###-#### Internet Inspection Request from: Jan Rice corrections made. ok to final. 1/5/2005 4:48:47 PM
|
Final | 12/29/2004 | 12/30/2004 | 12/30/2004 | A | FAIL |
Bob Reichert
|
|
|
Terry-call 1/2 hr ahead; Phone #: ###-#### Internet Inspection Request from: Jan Rice 314.17(A) pump diaconnect shall have ko seals installed,250.94 provide ufer access, 250.104(A) bond to metal water piping shall be provided, , 250.110 ground wire in service shall be attached, 110.27(A) dead-front shall be provided in service, 200.11 recepts shall be correct polarity in kitchen, master bath, and jetted tub area. 12/30/2004 9:45:32 AM
|
Electrical Rough-In | 8/16/2004 | 8/16/2004 | 8/16/2004 | P | PASS |
Jack Frank
|
|
|
###-#### - terry r/i ok see added p/s 8/16/2004 1:13:08 PM
|
Permanent Service | 8/16/2004 | 8/16/2004 | 8/16/2004 | P | PASS |
Jack Frank
|
|
|
p/s u/g new ok
|