Final | 12/16/2005 | 12/16/2005 | 12/16/2005 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Heather Packer no card to sign, open items taken care of, ok to final
|
Final | 11/21/2005 | 11/21/2005 | 11/21/2005 | P | PART |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Heather Packer walked job with electrician, the open items that shall be fixed:in-use cover on outside recpts, bond hot and cold pipes at water heaters, find listing on stage panel, get test results for gfi on main,add pull point on rooftop unit, strap fa panel conduit. Will recall when done, rest ok.
|
Electrical Rough-In | 11/9/2005 | 11/10/2005 | 11/10/2005 | A | PASS |
Pat Lass
|
|
|
Call Paul for questions; Phone #: ###-#### Internet Inspection Request from: Heather Packer
|
Electrical Rough-In | 10/18/2005 | 10/18/2005 | 10/18/2005 | P | PART |
Bob Reichert
|
|
|
ceiling insp.; Phone #: ###-#### Internet Inspection Request from: Heather Packer south 1/2 hall ceiling ok to cover
|
Electrical Rough-In | 10/12/2005 | 10/13/2005 | 10/13/2005 | P | PASS |
Bob Reichert
|
|
|
ceiling should be exposed after lunch. Thanks!; Phone #: ###-#### Internet Inspection Request from: Heather Packer ok to cover clg rm 105 front foyer
|
Electrical Rough-In | 10/11/2005 | 10/12/2005 | 10/12/2005 | A | PART |
Pat Lass
|
|
|
Ceiling insp.; Phone #: ###-#### Internet Inspection Request from: Heather Packer I approved 2 sections for cover. the front had tiles installed and the second section down the hall was not ready yet. I approved the 2 sections next to those areas.
|
Electrical Rough-In | 9/13/2005 | 9/14/2005 | 9/14/2005 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Heather ok to cover ceiling for rooms 141, 121 122, 123, 124, 125, 126, 127, 128, 129, looked at stage area in front and ok
|
Electrical Rough-In | 9/8/2005 | 9/9/2005 | 9/8/2005 | A | CANC |
Bob Reichert
|
|
|
ceiling insp.; Phone #: ###-#### Internet Inspection Request from: Heather Packer Inspection cancelled from web by: Heather Packer
|
Electrical Rough-In | 8/31/2005 | 9/1/2005 | 9/1/2005 | A | PART |
Bob Reichert
|
|
|
ceiling insp. Thanks!; Phone #: ###-#### Internet Inspection Request from: Heather Packer clg cover ok, see dwg, ok for covers in elect room
|
Electrical Rough-In | 8/30/2005 | 8/31/2005 | 8/31/2005 | A | PART |
Bob Reichert
|
|
|
ceiling insp.; Phone #: ###-#### Internet Inspection Request from: Heather Packer clg cover ok for rooms marked on print in office
|
Electrical Rough-In | 8/1/2005 | 8/2/2005 | 8/2/2005 | A | PART |
William E Thomas
|
|
|
ceiling///paul; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa south bathrooms only
|
Electrical Rough-In | 7/26/2005 | 7/27/2005 | 7/27/2005 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Heather Packer soffits so end auditorium and north half of foyer ok to cover
|
Electrical Rough-In | 7/7/2005 | 7/7/2005 | 7/7/2005 | P | PASS |
Bob Reichert
|
|
|
RI for walls. Thanks!; Phone #: ###-#### Internet Inspection Request from: Heather Packer front foyer walls only, and bath walls and clg ok to cover
|
Permanent Service | 6/24/2005 | 6/27/2005 | 6/27/2005 | P | PASS |
Bob Reichert
|
|
|
paul; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie asked contr to check w/ ipco for available fault current with xfmr being close to switchgear. contr will add 1 more ground clamp to water pipe coming in bldg. p/s u/g n ok
|
Electrical Rough-In | 6/10/2005 | 6/13/2005 | 6/13/2005 | A | PASS |
Bob Reichert
|
|
|
RI for walls. Thanks!; Phone #: ###-#### Internet Inspection Request from: Heather Packer e and w wall auditorium and elect room ok to cover
|
Electrical Rough-In | 6/2/2005 | 6/2/2005 | 6/2/2005 | P | PASS |
Bob Reichert
|
|
|
Wall rough-in. Thanks!; Phone #: ###-#### Internet Inspection Request from: Heather Packer sw and west wall ok to cover
|
Conference | 4/6/2005 | 4/6/2005 | 4/6/2005 | P | DONE |
Bob Reichert
|
|
|
###-#### - paul talked aqbout wireway and derate. Will get back to contr. tomorrow. 4/6/2005 4:17:26 PM
|
Electrical Rough-In | 3/15/2005 | 3/16/2005 | 3/16/2005 | A | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 3/15/2005 at 8:44:25 AM. Contact: ###-####. Mainly job walk to get familiar with job, pointed out foreign piping over elect equip in elect room, signed their inspection log 3/16/2005 9:53:53 AM
|
ELE-Aging Inspection | 12/27/2004 | 12/27/2004 | 12/27/2004 | P | NR |
Bob Reichert
|
|
|
doing block work. More u/g coming.
|
Electrical Rough-In | 9/16/2004 | 9/16/2004 | 9/16/2004 | P | PASS |
Joe Ray
|
|
|
Scheduled by a contractor via Hello! on 9/16/2004 at 7:36:41 AM. Contact: ###-####. concrete encased electrode ok to cover 9/16/2004 3:27:07 PM
|
Electrical Rough-In | 9/8/2004 | 9/8/2004 | 9/8/2004 | P | PASS |
Joe Ray
|
|
|
mike ###-#### 9/8/2004 9:13:52 AM
|
Conference | 9/7/2004 | 9/7/2004 | 9/7/2004 | P | CANC |
Joe Ray
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
Permanent Service | 8/31/2004 | 9/1/2004 | 9/1/2004 | P | PASS |
Joe Ray
|
|
|
Phone #: ###-#### Internet Inspection Request from: Heather Packer p/s ug n ok 9/1/2004 2:33:32 PM
|
Rough-In Permanent Service | 8/31/2004 | 8/31/2004 | 8/31/2004 | P | PASS |
Joe Ray
|
|
|
Scheduled by a contractor via Hello! on 8/31/2004 at 7:59:20 AM. Contact: ###-####. underground ok 8/31/2004 2:52:55 PM
|