Final | 2/2/2005 | 2/3/2005 | 2/3/2005 | A | PASS |
Jack Frank
|
|
|
ok 2/3/2005 8:13:38 AM
|
Final | 1/31/2005 | 1/31/2005 | 1/31/2005 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs cor. posted called needs to replace box in dinning rm they damaged 1/31/2005 4:33:40 PM
|
Final | 1/28/2005 | 1/28/2005 | 1/28/2005 | P | FAIL |
Jack Frank
|
|
|
Would like inspection asap. Thanks.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs cor. posted called 210.52(C) required outlet spacing counter in din rm, box fill and protect romex island counter, 210.12 arc-fault for bath circuit in bedrms,seal KOs in back of fixtures,a dn use connectors for cables and leave open so I can inspect, is outside ceiling fan approved for outside 1/28/2005 2:15:22 PM
|
Rough-In Permanent Service | 8/27/2004 | 8/30/2004 | 8/30/2004 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs r/i ok
p/s u/g new ok 8/30/2004 7:58:50 AM
|