Final | 11/4/2004 | 11/4/2004 | 11/4/2004 | P | PASS |
Jack Frank
|
|
|
###-#### Brad ok card signed 11/4/2004 1:02:34 PM
|
Electrical Rough-In | 10/27/2004 | 10/27/2004 | 10/27/2004 | P | PASS |
Jack Frank
|
|
|
brad---this is for above ceiling; Phone #: ###-#### Internet Inspection Request from: Linda Hartwell ceilings ok 10/27/2004 3:58:10 PM
|
Conference | 10/25/2004 | 10/26/2004 | 10/26/2004 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/25/2004 at 9:02:50 PM. Contact: ###-####. see added r/i 10/26/2004 1:35:26 PM
|
Electrical Rough-In | 10/26/2004 | 10/26/2004 | 10/26/2004 | P | PART |
Jack Frank
|
|
|
ceiling borders ok, cor. posted 300.11 needs own support wires, and shall not support cables from raceways or cables, 358.28 over 4 90s in emt, 330.30 strap mc
|
Electrical Rough-In | 9/10/2004 | 9/10/2004 | 9/10/2004 | P | PART |
Jack Frank
|
|
|
###-####- brad walls ok 9/10/2004 4:15:03 PM
|