Final | 1/26/2005 | 1/26/2005 | 1/26/2005 | P | PASS |
Jack Frank
|
|
|
dannette; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok 1/26/2005 1:08:16 PM
|
Electrical Rough-In | 10/4/2004 | 10/4/2004 | 10/4/2004 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/4/2004 at 10:45:08 AM. Contact: ###-####. ok see added p/s 10/4/2004 12:24:42 PM
|
Permanent Service | 10/4/2004 | 10/4/2004 | 10/4/2004 | P | PASS |
Jack Frank
|
|
|
p/s o/h rec. ok
|
Electrical Rough-In | 9/29/2004 | 9/30/2004 | 9/30/2004 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 9/29/2004 at 1:46:45 PM. Contact: ###-####. corrections not made needs nail plates and 1 1/4", remove phone and tv from below panel called 9/30/2004 12:20:06 PM
|
Rough-In Permanent Service | 9/27/2004 | 9/27/2004 | 9/27/2004 | P | FAIL |
Jack Frank
|
|
|
summer ###-#### cor. posted called 300.4 nail plates and 1 1/4", 110.26(F)(2) remove phone and tv from below p/s, 314.43 no nails, or screws in plastic boxes, 230.28 support mast 9/27/2004 3:39:01 PM
|