Final | 2/8/2005 | 2/8/2005 | 2/8/2005 | P | PASS |
Jack Frank
|
|
|
thanx jack see ya on the pool; Phone #: ###-#### Internet Inspection Request from: joe wheeler ok 2/8/2005 2:43:35 PM
|
Final | 2/5/2005 | 2/7/2005 | 2/7/2005 | A | PART |
Jack Frank
|
|
|
permit for pool is established thanx jack. ; Phone #: ###-#### Internet Inspection Request from: joe wheeler t/o ok no final needs clearence for sub panel,, remove low voltage cables above and drain below 2/7/2005 9:25:00 AM
|
Final | 2/4/2005 | 2/4/2005 | 2/4/2005 | P | NR |
Jack Frank
|
|
|
jack i need to get final inspection, but the pool system is not going to be ready for a couple of months due to weather. how do i notate this? please advise. cleaning crews will be in and out please call before arrival so i can make sure someone is there. thanx joe ; Phone #: ###-#### Internet Inspection Request from: joe wheeler called contractor will secure new permit for pool, so house can be finaled 2/4/2005 3:34:06 PM
|
Conference | 11/3/2004 | 11/3/2004 | 11/3/2004 | A | DONE |
Jack Frank
|
|
|
CONSULT ON POOL ELECTRICAL PANEL PLACEMENT THANX JACK; Phone #: ###-#### Internet Inspection Request from: joe wheeler answered ? over phone 11/3/2004 9:19:41 AM
|
Electrical Rough-In | 10/27/2004 | 10/27/2004 | 10/27/2004 | A | PART |
Jack Frank
|
|
|
pool bonding, i also have a trench that needs to be partially covered so concrete can be brought in. next to pool. thanx jack ; Phone #: ###-#### Internet Inspection Request from: joe wheeler part bond and u/g 10/27/2004 9:22:14 AM
|
Electrical Rough-In | 10/19/2004 | 10/19/2004 | 10/19/2004 | A | PART |
Jack Frank
|
|
|
pantry light, iron circuit a/c conduit. thanx jack; Phone #: ###-#### Internet Inspection Request from: joe wheeler ok 10/19/2004 8:43:18 AM
|
Electrical Rough-In | 10/18/2004 | 10/18/2004 | 10/18/2004 | A | PART |
Jack Frank
|
|
|
basement ready for cover. thanx jack; Phone #: ###-#### Internet Inspection Request from: joe wheeler ok except for mech. rm 10/18/2004 9:42:58 AM
|
Electrical Rough-In | 10/14/2004 | 10/14/2004 | 10/14/2004 | A | FAIL |
Jack Frank
|
|
|
reinspection on corrections thanx jack. joe; Phone #: ###-#### Internet Inspection Request from: joe wheeler all corrections not made box fill still, and 300.4(D) for low voltage 10/14/2004 9:16:13 AM
|
Electrical Rough-In | 10/14/2004 | 10/14/2004 | 10/14/2004 | P | PART |
Jack Frank
|
|
|
joe; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok 1st floor only told electrician if changes are made , that do not match approved plans call for for inspection of area changed 10/14/2004 12:38:20 PM
|
Electrical Rough-In | 10/12/2004 | 10/12/2004 | 10/12/2004 | A | FAIL |
Jack Frank
|
|
|
this is for upstairs only thanx jack ; Phone #: ###-#### Internet Inspection Request from: joe wheeler cor. posted met contractor 300.4, 314.16, 210.52(C) needs required spacing outlets left and right of kit sink, #14 awg on 20 amp circuit(vaccum outlets) cor posted on BLD permit for low voltage 300.4(D) 10/12/2004 2:28:15 PM
|
Electrical Rough-In | 9/29/2004 | 9/30/2004 | 9/30/2004 | P | PART |
Jack Frank
|
|
|
need to inspect soffit lighting for cover thanx jack; Phone #: ###-#### Internet Inspection Request from: joe wheeler ok 9/30/2004 4:10:25 PM
|
Permanent Service | 9/28/2004 | 9/29/2004 | 9/29/2004 | A | PASS |
Jack Frank
|
|
|
inspection for cocrete encased electrode and service; Phone #: ###-#### Internet Inspection Request from: joe wheeler
p/s u/g new ok 9/29/2004 8:38:25 AM
|
Electrical Rough-In | 9/28/2004 | 9/28/2004 | 9/28/2004 | A | PART |
Jack Frank
|
|
|
electrode ok for concrete cover
|
Temporary Service | 9/27/2004 | 9/28/2004 | 9/28/2004 | A | CANC |
Jack Frank
|
|
|
need inspection for concrete encased electrode; Phone #: ###-#### Internet Inspection Request from: joe wheeler see added r/i 9/28/2004 8:45:57 AM
|