Final | 2/10/2005 | 2/10/2005 | 2/10/2005 | P | PASS |
Pat Lass
|
|
|
Mark; Phone #: ###-#### Internet Inspection Request from: Jan Rice
could not find card 2/10/2005 3:06:51 PM
|
Permanent Service | 12/14/2004 | 12/14/2004 | 12/14/2004 | A | NR |
Pat Lass
|
|
|
will call in for pm 12/14/2004 9:27:28 AM
|
Permanent Service | 12/14/2004 | 12/14/2004 | 12/14/2004 | P | PASS |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Linda Hartwell
P/S O/H N Ok 12/14/2004 12:25:22 PM
|
Electrical Rough-In | 12/8/2004 | 12/8/2004 | 12/8/2004 | A | PASS |
Pat Lass
|
|
|
Write a surevy and ok R/I. call me JMS
posted survey and approved R/I 12/8/2004 9:16:53 AM
|
Rough-In Permanent Service | 12/7/2004 | 12/8/2004 | 12/8/2004 | A | CANC |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ken Litzinger contractor called to cancel inspection
|
Rough-In Permanent Service | 12/7/2004 | 12/7/2004 | 12/7/2004 | P | FAIL |
Jack Frank
|
|
|
Re-inspection. Please inspect asap. Thank you.; Phone #: ###-#### Internet Inspection Request from: Ken Litzinger cor. and reinspection fee posted all violation not corrected, outlet spacing, staple within 8"or 12" of boxes 334.30, 110.14 shall not mix copper and alum under same lug at p/s, 210.70(A)(3) LIGHT FOR FURNACE called u/g ok for cover only 12/7/2004 1:06:18 PM
|
Electrical Rough-In | 12/3/2004 | 12/3/2004 | 12/3/2004 | P | FAIL |
Pat Lass
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
boxes for 3 way upstairs overfilled.
recep spacing off in several places.
underground to garage not inspected.
service riser enters the top of service equipment through a rubber gasket not a hub.
called got no answer. 12/3/2004 2:07:58 PM
|