Final | 2/16/2005 | 2/16/2005 | 2/16/2005 | P | PASS |
Bob Reichert
|
|
|
allan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore corrections made , ok to final 2/16/2005 12:28:19 PM
|
Final | 2/11/2005 | 2/11/2005 | 2/11/2005 | P | FAIL |
Bob Reichert
|
|
|
allen; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles 110.12(C) there shall be no damaged parts(service riser), 352.30(A) rnc shall be supported within 3" of box, 406.4 recepts shall be securely fastened called contr, left corr notice 2/11/2005 12:21:11 PM
|
Electrical Rough-In | 10/26/2004 | 10/27/2004 | 10/27/2004 | A | PASS |
Bob Reichert
|
|
|
Alan-; Phone #: ###-#### Internet Inspection Request from: Cheryl Baumgartner p/s u/g n ok,ri cover ok 10/27/2004 8:57:15 AM
|