Electrical Rough-In | 11/18/2004 | 11/18/2004 | 11/18/2004 | A | PASS |
Jack Frank
|
|
|
cei,ings ok
|
Final | 11/17/2004 | 11/18/2004 | 11/18/2004 | A | NR |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 11/17/2004 at 4:33:15 PM. Contact: ###-####. see added r/i 210.8 (B)(3) shall provide gfci for all 15,20 amp 120 volt recepts 11/18/2004 9:54:33 AM
|
Final | 11/18/2004 | 11/18/2004 | 11/18/2004 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 11/18/2004 at 9:46:48 AM. Contact: ###-####. ok to final, corrections made. 11/18/2004 4:27:00 PM
|
Electrical Rough-In | 11/16/2004 | 11/17/2004 | 11/17/2004 | A | FAIL |
Bob Reichert
|
|
|
ceiling cover inspection please////doug; Phone #: ###-#### Internet Inspection Request from: Barba 314.23 boxes shall be supported,348.30 flex shall be supported and fastened, 358.30 emt shall be supported and secured, 314.25 covers shall be provided, 110.26(A) clearance for work space shall be provided, 110.22 disconnects shall be identified, 110.12 work shall be done neatly and in aworkmanlike manner 11/17/2004 9:40:28 AM
|
Conference | 11/15/2004 | 11/16/2004 | 11/16/2004 | A | DONE |
Bob Reichert
|
|
|
Doug-In the Food Court; Phone #: ###-#### Internet Inspection Request from: Cheryl Baumgartner told contr. clg must be up to code within 3' of tile or work area. 11/16/2004 9:00:56 AM
|
Electrical Rough-In | 11/3/2004 | 11/3/2004 | 11/3/2004 | P | PASS |
Bob Reichert
|
|
|
Douglas Electric/Kelly ; Phone #: ###-#### Internet Inspection Request from: Cheryl Baumgartner walls ok to cover 11/3/2004 12:47:06 PM
|