Permit Information
Permit NumberELE04-03507
StatusFinaled
Name B & J ELECTRIC INC
Site Address 7337 W NORTHVIEW ST
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Alteration: Interior Remodel of outlet, switches and lights.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/9/20053/11/20053/11/2005PPASS
DetailsWilliam E Thomas
Phone #: ###-#### Internet Inspection Request from: Joe Thomas
Electrical Rough-In2/17/20052/17/20052/17/2005AFAIL
DetailsJack Frank
ceiling cover for grid in phase 2; Phone #: ###-#### Internet Inspection Request from: Joe Thomas cor. posted called 300.11(ABC) same corrections posted 12-09-04 2/17/2005 11:00:56 AM
Electrical Rough-In2/17/20052/17/20052/17/2005PPASS
DetailsJack Frank
cover of ceiling grid in phase 2; Phone #: ###-#### Internet Inspection Request from: Joe Thomas 2/17/2005 1:30:07 PM
Electrical Rough-In2/16/20052/16/20052/16/2005PFAIL
DetailsMike Kinnear
Cover for ceiling tile; Phone #: ###-#### Internet Inspection Request from: Joe Thomas corrections not made called joe he meet me & he to fix corrections 2/16/2005 4:01:23 PM
Electrical Rough-In2/15/20052/15/20052/15/2005PFAIL
DetailsBob Reichert
Ceiling inspection for phase 2 cover of ceiling.; Phone #: ###-#### Internet Inspection Request from: Joe Thomas 358.30(A) emt shall be supported within 3' of box, 314.17(A) openings shall be closed (heater), 300.11(A) independent ceiling wires shall be identified, 300.11(2)(B) raceways shall not be used as support for non-electric equipment. Note: support wires for fixtures require min 2 wires for seismic 2/15/2005 2:12:31 PM
Electrical Rough-In1/24/20051/24/20051/24/2005PPASS
DetailsBob Reichert
rough in for walls in phase 2; Phone #: ###-#### Internet Inspection Request from: Joe Thomas ok to cover steel walls 1/24/2005 1:16:11 PM
Electrical Rough-In12/29/200412/29/200412/29/2004PPART
DetailsBob Reichert
ceiling inspection for cover where ceiling grid is installed in phase 1; Phone #: ###-#### Internet Inspection Request from: Joe Thomas ok to cover ceiling only for phase 1 where grid is up. Corrections made. 12/29/2004 1:52:47 PM
Electrical Rough-In12/9/200412/9/200412/9/2004PFAIL
DetailsJack Frank
approval for ceiling cover in areas with grid ceiling; Phone #: ###-#### Internet Inspection Request from: Joe Thomas cor. posted called, 300.11(ABC) raceways or cables shall not support cables or raceways, if wires are used do as code noted states 314.23(D) shall support boxes, 110.26(F)(1) provide clearence for all panels (panels above ceiling grid, all wiring shall meet 517 for patient care area 800.2,760.2,725.2 remove abandoned cables, 800.5&6, 760.5&6, 725.5&6 support, protect, and install as code noted states B C C no violations retained 12/9/2004 2:16:12 PM
Electrical Rough-In12/8/200412/8/200412/8/2004PNR
DetailsBob Reichert
Approval for cover on grid ceiling; Phone #: ###-#### Internet Inspection Request from: Joe Thomas talked to contr. and told him he needs ko seals in boxes,strapping for mc cable over panel, and conduit, also to determine what abandoned cabling in ceiling needs to be removed. He says that job will be done in phases which is why one fixture is covered by temp wall. 12/8/2004 2:00:16 PM
Electrical Rough-In11/10/200411/10/200411/10/2004APART
DetailsJack Frank
Rough in for walls of dentists office; Phone #: ###-#### Internet Inspection Request from: Joe Thomas ok 11/10/2004 9:40:28 AM
Electrical Rough-In11/8/200411/9/200411/9/2004AFAIL
DetailsPat Lass
###-#### Rough in for walls of dentists office. Project is being done in 2 phases. This is for the 1st phase.; Phone #: ###-#### Internet Inspection Request from: Joe Thomas 11/9/2004 8:07:01 AM
300.4 Protection Against Physical Damage.
Where subject to physical damage, conductors shall be adequately protected.
(D) Cables and Raceways Parallel to Framing Members.
11/9/2004 9:52:55 AM