DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/18/20069/19/20069/19/2006APASS
DetailsPat Lass
Scheduled by a contractor via Hello! on 9/18/2006 at 2:48:28 PM. Contact: ###-####.
Final7/24/20067/25/20067/25/2006AFAIL
DetailsPat Lass
Scheduled by a contractor via Hello! on 7/24/2006 at 1:36:20 PM. Contact: ###-####
trim for closet light
in-use covers outside
cover for recep for jetted tub
Electrical Rough-In10/31/200510/31/200510/31/2005PPASS
DetailsPat Lass
Scheduled by a contractor via Hello! on 10/31/2005 at 8:15:25 AM. Contact: ###-####.
Electrical Rough-In10/27/200510/28/200510/28/2005PFAIL
DetailsWilliam E Thomas
Scheduled by a contractor via Hello! on 10/27/2005 at 11:24:29 AM. Contact: ###-####.
225.30, 225.31,225.36
Rough-In Permanent Service7/27/20057/27/20057/27/2005PPASS
DetailsPat Lass
###-####. Scheduled by a contractor via Hello! on 7/27/2005 at 9:52:56 AM. Contact: ###-####.
P/S O/H R Ok
Rough-In Permanent Service7/26/20057/27/20057/27/2005AFAIL
DetailsPat Lass
Scheduled by a contractor via Hello! on 7/26/2005 at 3:59:37 PM. Contact: ###-####.
GEC to go to neutral
Rough-In Permanent Service7/25/20057/26/20057/26/2005AFAIL
DetailsPat Lass
Scheduled by a contractor via Hello! on 7/25/2005 at 1:33:51 PM. Contact: ###-####
use listed MBJ
use plastic romex connector on GEC and acorn on electrode.
will eather move panel or make a utility room behind closet.
Permanent Service7/20/20057/22/20057/22/2005AFAIL
DetailsPat Lass
###-####. Scheduled by a contractor via Hello! on 7/20/2005 at 12:27:38 PM. Contact: ###-####.
314.17 Conductors Entering Boxes, Conduit Bodies, or Fittings.
Conductors entering boxes, conduit bodies, or fittings shall be protected from abrasion and shall comply with 314.17(A) through (D).
300.15 Boxes, Conduit Bodies, or Fittings - Where Required.
Fittings and connectors shall be used only with the specific wiring methods for which they are designed and listed.
230.24 Clearances.
Service-drop conductors shall not be readily accessible and shall comply with 230.24(A) through (D) for services not over 600 volts, nominal.
230.26 Point of Attachment.
In no case shall this point of attachment be less than 3.0 m (10 ft) above finished grade.
Electrical Rough-In4/1/20054/1/20054/1/2005PPASS
DetailsPat Lass
Scheduled by a contractor via Hello! on 4/1/2005 at 9:02:11 AM. Contact: ###-####.
Electrical Rough-In3/14/20053/15/20053/15/2005PPASS
DetailsPat Lass
niki; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
Electrical Rough-In1/26/20051/26/20051/26/2005PPART
DetailsPat Lass
andy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
west end ok 1/26/2005 2:09:12 PM
Electrical Rough-In1/19/20051/21/20051/21/2005PNR
DetailsPat Lass
niki; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
had conf about circuiting and location of receps 1/21/2005 1:20:41 PM