Final | 3/30/2005 | 3/30/2005 | 3/30/2005 | P | PASS |
Pat Lass
|
|
|
jack; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
NO CARD 3/30/2005 2:41:12 PM
|
Final | 3/25/2005 | 3/25/2005 | 3/25/2005 | P | FAIL |
Pat Lass
|
|
|
jack; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
GFCI protect bathroom receps
lock out for hard wired oven 3/25/2005 2:00:16 PM
|
Final | 3/21/2005 | 3/21/2005 | 3/21/2005 | P | FAIL |
Bob Reichert
|
|
|
jack; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left correction notice, 314.15(A) emt connectors and fittings shall be listed for wet locations, 408.4 panel schedule shall have details, 406.5 recepts shall have faceplate, 406.2 range recpt shall be provided,210.11(C)(2) laundry recpt shall work, 210.70(A)(2)(b) light shall work at garage, 300.5 shall uncover u/g to garage to verify depth of wiring. 3/21/2005 2:29:48 PM
|
Electrical Rough-In | 1/11/2005 | 1/12/2005 | 1/12/2005 | A | PASS |
Pat Lass
|
|
|
Jack-call before you go so he can let you in; Phone #: ###-#### Internet Inspection Request from: Jan Rice
|
Electrical Rough-In | 1/10/2005 | 1/11/2005 | 1/11/2005 | P | FAIL |
Jack Frank
|
|
|
please call half hour prior to inspection so he can let ya in///jack; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. posted met contractor 300.4(A)(1)&(D), 210.52(C)(1) countertop outlet spacing, 210.52(D)&210.11(C)(3) outlet within 3ft of sink,and 20 amp bath circuit, 250.140 shall use SE type cable from P/S or 10/3 romex for cook top 1/11/2005 2:09:46 PM
|