Final | 5/25/2005 | 5/25/2005 | 5/25/2005 | P | PASS |
Bob Reichert
|
|
|
mike ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok to final
|
Final | 5/23/2005 | 5/24/2005 | 5/24/2005 | A | FAIL |
Bob Reichert
|
|
|
###-#### - mike 422.31(B) breaker lo for dishwasher, 422.16 cord for disposal shall be installed, 314.20 flush recpt under sink, 210.52(E) gfci rcpt shall be installed at back of house
|
Electrical Rough-In | 1/21/2005 | 1/24/2005 | 1/24/2005 | A | PASS |
Bob Reichert
|
|
|
Mike-partial-ufer insp.; Phone #: ###-#### Internet Inspection Request from: Jan Rice left survey for 314.43 light box shall not have screw inside of box, 314.20 box shall be flush. Called contractor. Ufer ok. p/s u/g n ok 1/24/2005 8:36:48 AM
|
Electrical Rough-In | 1/10/2005 | 1/10/2005 | 1/10/2005 | P | PASS |
Bob Reichert
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Jan Rice asked superintendent to flush out light and recpt on outside of house. ufer ground ready to pour. I said we want to see concrete before we approve power. ok to cover. perm service later. 1/10/2005 2:05:29 PM
|