Final | 6/2/2005 | 6/2/2005 | 6/2/2005 | P | PASS |
Bob Reichert
|
|
|
dennis; Phone #: ###-#### Note: please ring the doorbell a couple times-he will be asleep Internet Inspection Request from: Cathy Chiles corrections made, ok to final
|
Final | 6/1/2005 | 6/1/2005 | 6/1/2005 | P | FAIL |
Jack Frank
|
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa cor.posted met owner 314.20 boxes shall be flush with combustible material, 410.8 (A&B) enclosed type fixture no pendents allowed MB closet, 210.12 arc fault all circuits in M bed
|
Electrical Rough-In | 2/4/2005 | 2/7/2005 | 2/7/2005 | A | PASS |
Bob Reichert
|
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Barbara Moore corrections made, ric ok 2/7/2005 9:45:45 AM
|
Electrical Rough-In | 2/2/2005 | 2/3/2005 | 2/3/2005 | A | FAIL |
Bob Reichert
|
|
|
Dennis; Phone #: ###-#### Internet Inspection Request from: Jan Rice Bcc all wires shall be made up in boxes,314.17 nm cable shall be stapled within 8" of box. 2/3/2005 8:49:51 AM
|