Final | 6/30/2005 | 6/30/2005 | 6/30/2005 | P | PASS |
Bob Reichert
|
|
|
HAD TO PULL A PERMIT TO GET AN INSPECTION SO WE COULD LET THE HOME SELLER KNOW WHAT NEEDED TO BE BROUGHT UP TO CODE..WE NEVER ENDED UP DOING ANY WORK.; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen ok to final
|
Final | 2/1/2005 | 2/2/2005 | 2/2/2005 | A | NH |
Mike Kinnear
|
|
|
contact Bob Kiah he is the real estate broker ###-#### for entrance Internet Inspection Request from: Tyler Bowen called no answer called RME they call us for appointment to inspect job 2/2/2005 9:36:00 AM
|
Permanent Service | 2/2/2005 | 2/2/2005 | 2/2/2005 | P | FAIL |
Bob Reichert
|
|
|
Please call Bob Kiah prior to heading out so he can meet you to unlock the house ###-####..; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen Called contr to gain entry, he sent realtor out. The following need fixed as a minimum. 110.12(A) unused opening in bottom of meter needs closed. Ground wire entering 1" threaded opening. 440.22(C) a/c fuses shall not exceed mfgr's value, 250.56 single electrode shall be supplemented by additional one ,200.7 white wire for grounded ckt only, 310.16 max ampacity #14 wire to be 15A, 250.86 raceway shall be grounded thru concentric,334.30 nm cable shall be protected for washer and dryer, 334.30(A) metal conduit shall be strapped within 3' of meter,250.104 metal water piping shall be bonded, 408.4 panel shall have directory, 200.6(B) neutral shall be identified, BCC shall post job sticker. 2/2/2005 4:31:37 PM
|