Final | 2/17/2005 | 2/18/2005 | 2/18/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 2/17/2005 at 3:39:05 PM. Contact: ###-####. called contr to put on one switch cover and to tighten gfci. ok to final 2/18/2005 11:13:51 AM
|
Final | 2/17/2005 | 2/17/2005 | 2/17/2005 | A | NR |
Bob Reichert
|
|
|
please call 1/2 hr before inspection will met you there thank you; Phone #: ###-#### Internet Inspection Request from: Todd Holbrook corrections not made 2/17/2005 10:01:18 AM
|
Final | 2/16/2005 | 2/16/2005 | 2/16/2005 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 2/16/2005 at 8:29:35 AM. 314.20 boxes shall be within 1/4" of surface, 314.21 drywall shall be repaired at switch and outlets to less than 1/8", 314.25 boxes shall have covers installed, 314.23(C) boxes shall be rigidly installed in finished surface, 404(D) fixture over tub shall be listed for damp location, 406.8(C) recpt shall not be installed within bath tub area, 110.3(B) all equipment shall be listed, 110.26(A)(2) workspace shall be 30" wide in front of panel. 2/16/2005 4:41:48 PM
|
Permanent Service | 2/4/2005 | 2/7/2005 | 2/7/2005 | A | NH |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 2/4/2005 at 12:05:36 PM. Contact: ###-####. no access, called contr. told to call in for pm. 2/7/2005 8:53:37 AM
|
Permanent Service | 2/7/2005 | 2/7/2005 | 2/7/2005 | P | PASS |
Bob Reichert
|
|
|
jeremy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore p/s from exst meter pak n ok 2/7/2005 12:52:01 PM
|
Permanent Service | 2/2/2005 | 2/3/2005 | 2/3/2005 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 2/2/2005 at 11:32:36 AM. Contact: ###-####. 110.26 (F) there shall be no foreign pipes above the dedicated equipment space. 2/3/2005 10:26:54 AM
|
Permanent Service | 2/1/2005 | 2/2/2005 | 2/2/2005 | A | FAIL |
Jack Frank
|
|
|
Todd ###-#### need information called left message where is the p/s? no ID tag 2/2/2005 10:09:57 AM
|