Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE05-00344
StatusFinaled
Name CITYLIGHT ELECTRIC LLC
Site Address 1023 S CURTIS RD
Project Name 
Customer Number 
ePlanReview 
Description
Wire existing buildingwith new MC cable & add outlets & switches & lights per initial cert of value $4,722///2/2/05 BAS
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/9/20063/9/20063/9/2006PPASS
DetailsMike Kinnear
rick; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa correction made ok final
Final3/8/20063/8/20063/8/2006PFAIL
DetailsJack Frank
Scheduled by a contractor via Hello! on 3/8/2006 at 11:12:38 AM. corr. posted called reinspection fee due, 250.32(B)(1) shall isolate grds and neutrals at p/s, 250.8 no SMS allowed, 250.50,52(A)(1)or104(A)(1) grd or bond water system, 312.5 needs conn for GEC, 110.3(B) use manufactures breakers only,408.4 circuit directory, 250.130 open grd gfci recept in restrm contractor has 5 working days too correct, complete, and call for reinspection
ELE-Aging Inspection2/22/20062/22/20062/22/2006 NR
DetailsJack Frank
ELE-Aging Inspection12/19/200512/19/200512/19/2005 PART
DetailsJack Frank
called corrections made contractor will schedule
ELE-Aging Inspection10/17/200510/17/200510/18/2005 DONE
DetailsJack Frank
called if corrections not made power may be turned off
ELE-Aging Inspection8/17/20058/17/20058/17/2005 PART
DetailsJack Frank
called contractor will correct and call for inspection , gave him one week to get work done
ELE-Aging Inspection5/25/20055/25/20055/25/2005 PART
DetailsJack Frank
called left message
Rough-In Permanent Service2/2/20052/2/20052/2/2005PPART
DetailsJack Frank
Please call at least 20 mins prior to inspection///Rick; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called left message 2/2/2005 12:25:20 PM r/i ok, met with contractor needs grd rods and water system grd at p/s no sms, needs neutral and equip grd kits for p/s switch no violations retained note p/s was done without permit awhile back 2/2/2005 1:31:19 PM