Final | 3/9/2006 | 3/9/2006 | 3/9/2006 | P | PASS |
Mike Kinnear
|
|
|
rick; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa correction made ok final
|
Final | 3/8/2006 | 3/8/2006 | 3/8/2006 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 3/8/2006 at 11:12:38 AM. corr. posted called reinspection fee due, 250.32(B)(1) shall isolate grds and neutrals at p/s, 250.8 no SMS allowed, 250.50,52(A)(1)or104(A)(1) grd or bond water system, 312.5 needs conn for GEC, 110.3(B) use manufactures breakers only,408.4 circuit directory, 250.130 open grd gfci recept in restrm contractor has 5 working days too correct, complete, and call for reinspection
|
ELE-Aging Inspection | 2/22/2006 | 2/22/2006 | 2/22/2006 | | NR |
Jack Frank
|
|
|
|
ELE-Aging Inspection | 12/19/2005 | 12/19/2005 | 12/19/2005 | | PART |
Jack Frank
|
|
|
called corrections made contractor will schedule
|
ELE-Aging Inspection | 10/17/2005 | 10/17/2005 | 10/18/2005 | | DONE |
Jack Frank
|
|
|
called if corrections not made power may be turned off
|
ELE-Aging Inspection | 8/17/2005 | 8/17/2005 | 8/17/2005 | | PART |
Jack Frank
|
|
|
called contractor will correct and call for inspection , gave him one week to get work done
|
ELE-Aging Inspection | 5/25/2005 | 5/25/2005 | 5/25/2005 | | PART |
Jack Frank
|
|
|
called left message
|
Rough-In Permanent Service | 2/2/2005 | 2/2/2005 | 2/2/2005 | P | PART |
Jack Frank
|
|
|
Please call at least 20 mins prior to inspection///Rick; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called left message 2/2/2005 12:25:20 PM r/i ok, met with contractor needs grd rods and water system grd at p/s no sms, needs neutral and equip grd kits for p/s switch no violations retained note p/s was done without permit awhile back 2/2/2005 1:31:19 PM
|