Final | 5/4/2005 | 5/5/2005 | 5/5/2005 | A | PASS |
Jack Frank
|
|
|
justin; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok no card 5/5/2005 8:32:42 AM
|
Final | 5/3/2005 | 5/3/2005 | 5/3/2005 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 5/3/2005 at 8:01:57 AM. Contact: ###-####. cor. posted met contractor 250.8 no SMS for grds or bonds, 250.148 grd metal boxes, needs UL listed RT fittings, 210.5A B C 314. 29 access to box, 300.10&12 314.14 needs access to boxes with fixtures mounted over them 5/3/2005 3:11:05 PM
|
Permanent Service | 3/25/2005 | 3/25/2005 | 3/25/2005 | P | PASS |
Jack Frank
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Moore p/s u/g new ok 3/25/2005 3:07:16 PM
|
Electrical Rough-In | 3/7/2005 | 3/8/2005 | 3/8/2005 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 3/7/2005 at 3:44:54 PM. ceiling ok 3/8/2005 8:28:15 AM
|
Electrical Rough-In | 3/7/2005 | 3/7/2005 | 3/7/2005 | P | FAIL |
Pat Lass
|
|
|
cover inspection///mike; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
over 400 deg. of bend in raceway 3/7/2005 1:14:18 PM
|
Electrical Rough-In | 2/7/2005 | 2/7/2005 | 2/7/2005 | P | PART |
Jack Frank
|
|
|
Gary-underground; Phone #: ###-#### Internet Inspection Request from: Jan Rice ok inside only 2/7/2005 12:07:19 PM
|