Permit NumberELE05-00459
StatusFinaled
Name HS ELECTRIC
Site Address 110 S COTTERELL DR
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/9/20056/10/20056/10/2005APASS
DetailsJack Frank
henry; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok corrections made
Final6/7/20056/7/20056/7/2005PPART
DetailsJack Frank
henry; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa temp occupancy for house ok cor. jtub shall be eired per manufactures instructions 2, 20 amp circuits
Final6/2/20056/3/20056/3/2005AFAIL
DetailsJack Frank
henry; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa cor. posted called needs instructions for j-tub, is paddle fan listed for outdoors, 250.148 grd metal boxes island, 300.10&314.3 no metal raceways in plastic boxes mech. rm furnace, 200.6&7 ID white in cables as phase where used as, 404.4 WP for outdoor switches, 408.4 label panels correctly, no power to recept front entry, wire DW
Electrical Rough-In4/22/20054/22/20054/22/2005PPART
DetailsJack Frank
posted a correction for owner on wiring done without permit and inspections he requested the correction notice, prior owner of house did the work in violation of NEC
Electrical Rough-In4/6/20054/6/20054/6/2005PPASS
DetailsJack Frank
henry; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok corrections made 4/6/2005 12:53:14 PM
Electrical Rough-In4/4/20054/5/20054/5/2005AFAIL
DetailsJack Frank
henry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. posted called 210.52(A),(B),(D) required outlets for wall space, only what code allows on small appliance brach circuits, all recepts in M bath shall be on bath 20 amp, 300.4(A)(1)&(D) nail plates and 11/4", 314.16 box fill notice for owner 300.4 nail plates and 11/4" bushings for cables, connectors for ENT reinspection fee due 4/5/2005 10:55:07 AM
Electrical Rough-In4/1/20054/4/20054/4/2005AFAIL
DetailsBob Reichert
henry; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles met elect, left corr notice, 210.52(A)(2) wall space over 2' shall have recpt, 210.52(H) hall shall have recpt, 406.8(C) there shall be no recpt over bath tub, 314.6 boxes shall not be over-filled 4/4/2005 8:57:57 AM
Electrical Rough-In4/1/20054/1/20054/1/2005PNR
DetailsJack Frank
henry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore lots of things wrong called contractor, he will reschedule inspection and meet me for conference 4/1/2005 3:52:23 PM
Electrical Rough-In3/7/20053/8/20053/8/2005PPART
DetailsJack Frank
henry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore conference ok r/i for garage ok only 3/8/2005 12:24:45 PM