Permit Information
Permit NumberELE05-00462
StatusFinaled
Name ANGEL'S ELECTRIC
Site Address 2307 W JEFFERSON ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/1/20066/2/20066/2/2006APASS
DetailsPat Lass
###-#### chad
Final5/23/20065/26/20065/26/2006AFAIL
DetailsJack Frank
chad ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
250.148 grd metal cutin box kit,314.17(B) needs conn for cutin box, 110.3(A) shall replace plastic box damaged back side peninsular counter, 210.52(B) shall install required small appliance branch circuits for kit ,din as code noted states min 2 circuits shall serve countertops outlets 408.4 panel schedule shall match circiut numbers on deadfront and be specfic as to purpose cow
reinspection fee called
Final5/1/20065/5/20065/5/2006PFAIL
DetailsPat Lass
chad ; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
Kitchen and upstairs bathroom 210.8 GFCI
210.52 required recep on ene of peninsular counter.
406.3 ungrounded recep by upstairs water heater.
Rough-In Permanent Service4/21/20054/22/20054/22/2005PPASS
DetailsPat Lass
chad; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
R/I Ok
P/S O/H R Ok 4/22/2005 1:07:21 PM
Rough-In Permanent Service4/19/20054/20/20054/20/2005PFAIL
DetailsPat Lass
chad; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
box fill
unused oppenings
outer sheath outside box
stiff leg on mast
grounding bus in sub panel
210.52
2 circuits for kitchen counter
use proper fitting on cable from main disconnect to sub panel
total reinspect required. 4/20/2005 4:13:46 PM
Electrical Rough-In4/14/20054/18/20054/18/2005PNR
DetailsBob Reichert
Scheduled by a contractor via Hello! on 4/14/2005 at 3:39:20 PM. Contact: ###-####. called contr, no access, looked thru window and told contr all make-up had to be done before inspection anyway. He will call back for rip when ready. All the boxes had nm cable coiled up and not made up. 4/18/2005 12:57:27 PM
Conference2/14/20052/16/20052/16/2005PPART
DetailsPat Lass
###-#### chad 1:00 pm. 2/15/2005 1:56:23 PM
prestart conf. 2/16/2005 2:08:52 PM