Final | 6/1/2006 | 6/2/2006 | 6/2/2006 | A | PASS |
Pat Lass
|
|
|
###-#### chad
|
Final | 5/23/2006 | 5/26/2006 | 5/26/2006 | A | FAIL |
Jack Frank
|
|
|
chad ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie 250.148 grd metal cutin box kit,314.17(B) needs conn for cutin box, 110.3(A) shall replace plastic box damaged back side peninsular counter, 210.52(B) shall install required small appliance branch circuits for kit ,din as code noted states min 2 circuits shall serve countertops outlets 408.4 panel schedule shall match circiut numbers on deadfront and be specfic as to purpose cow reinspection fee called
|
Final | 5/1/2006 | 5/5/2006 | 5/5/2006 | P | FAIL |
Pat Lass
|
|
|
chad ; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa Kitchen and upstairs bathroom 210.8 GFCI 210.52 required recep on ene of peninsular counter. 406.3 ungrounded recep by upstairs water heater.
|
Rough-In Permanent Service | 4/21/2005 | 4/22/2005 | 4/22/2005 | P | PASS |
Pat Lass
|
|
|
chad; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
R/I Ok
P/S O/H R Ok 4/22/2005 1:07:21 PM
|
Rough-In Permanent Service | 4/19/2005 | 4/20/2005 | 4/20/2005 | P | FAIL |
Pat Lass
|
|
|
chad; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
box fill
unused oppenings
outer sheath outside box
stiff leg on mast
grounding bus in sub panel
210.52
2 circuits for kitchen counter
use proper fitting on cable from main disconnect to sub panel
total reinspect required. 4/20/2005 4:13:46 PM
|
Electrical Rough-In | 4/14/2005 | 4/18/2005 | 4/18/2005 | P | NR |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 4/14/2005 at 3:39:20 PM. Contact: ###-####. called contr, no access, looked thru window and told contr all make-up had to be done before inspection anyway. He will call back for rip when ready. All the boxes had nm cable coiled up and not made up. 4/18/2005 12:57:27 PM
|
Conference | 2/14/2005 | 2/16/2005 | 2/16/2005 | P | PART |
Pat Lass
|
|
|
###-#### chad 1:00 pm. 2/15/2005 1:56:23 PM
prestart conf. 2/16/2005 2:08:52 PM
|