Permanent Service | 2/23/2005 | 2/24/2005 | 2/24/2005 | A | FAIL |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 2/23/2005 at 11:47:00 AM. Contact: ###-####.
no main bonding jumper.
ground rods not flush.
run #4 to water.
bond mast. 2/24/2005 10:02:21 AM
|
Permanent Service | 2/24/2005 | 2/24/2005 | 2/24/2005 | P | PASS |
Pat Lass
|
|
|
doug; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
P/S O/H R Ok 2/24/2005 3:56:24 PM
|