Final | 4/28/2005 | 4/29/2005 | 4/29/2005 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### x Internet Inspection Request from: David Nelson ok 4/29/2005 10:31:11 AM
|
Permanent Service | 2/28/2005 | 3/1/2005 | 3/1/2005 | A | PASS |
Jack Frank
|
|
|
david; Phone #: ###-#### Internet Inspection Request from: Barbara Moore p/s u/g new ok 3/1/2005 11:39:43 AM
|
Electrical Rough-In | 2/24/2005 | 2/24/2005 | 2/24/2005 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 2/24/2005 at 7:29:45 AM. Contact: ###-####. ok 2/24/2005 11:34:08 AM
|
Electrical Rough-In | 2/22/2005 | 2/23/2005 | 2/23/2005 | A | FAIL |
Jack Frank
|
|
|
David; Phone #: ###-#### Internet Inspection Request from: Jan Rice cor. posted called 300.4 nail plates and 11/4", 314.17 replace boxes with broken out cable clamps, and sheath shall extent 1/4" into boxes and clamps, 210.52(A)&(B) required outlets for wall space, and dinning rm outlets on small appliance brach circuit, complete all wiring, 210.52(D) outlets within 3ft of bath sinks 2/23/2005 12:04:15 PM
|