Final | 7/1/2005 | 7/1/2005 | 7/1/2005 | P | PASS |
Mike Kinnear
|
|
|
bill; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok final
|
Final | 6/30/2005 | 6/30/2005 | 6/30/2005 | P | FAIL |
Mike Kinnear
|
|
|
bill; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie correction nec 210.52 6ft wall spacing print shows area with built in cabinets no cabinets installed
|
Permanent Service | 6/28/2005 | 6/28/2005 | 6/28/2005 | A | PASS |
Mike Kinnear
|
|
|
p/s u/g n ok
|
Electrical Rough-In | 6/10/2005 | 6/13/2005 | 6/13/2005 | A | PART |
Jack Frank
|
|
|
concrete cover- gregg; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok for dirt cover
|
Permanent Service | 6/4/2005 | 6/6/2005 | 6/6/2005 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/4/2005 at 1:08:07 PM. Contact: ###-####. electrode ok for concrete cover
|
Rough-In Permanent Service | 4/5/2005 | 4/5/2005 | 4/5/2005 | P | PART |
Mike Kinnear
|
|
|
###-#### - bill ok cover ri p/s fail no ufer ground 4/6/2005 10:40:43 AM
|
Rough-In Permanent Service | 4/1/2005 | 4/4/2005 | 4/4/2005 | A | FAIL |
Jack Frank
|
|
|
bill ###-#### cor. posted called terminate GEC at neutral bus too many wires under one staples, cables stapled on edge, nail plates and 11/4 inches note will need inspection when floor heating cable is installed 4/4/2005 10:19:18 AM
|
Rough-In Permanent Service | 3/30/2005 | 3/31/2005 | 3/31/2005 | A | FAIL |
Jack Frank
|
|
|
Bill ###-#### cor. posted called 210.52(A)&(B) outlet spacing and only what code allows on kit circuit, 300.4(A)(1)&(D), 250.24 terminate GEC to neutral bus, use approved crimp tool 3/31/2005 10:28:12 AM
|
Electrical Rough-In | 2/28/2005 | 3/1/2005 | 3/1/2005 | A | PASS |
Mike Kinnear
|
|
|
Kitchen under slab pipe inspection please///Jim ###-#### ok cover under slab conduit 3/1/2005 9:08:38 AM
|