Final | 7/28/2005 | 7/28/2005 | 7/28/2005 | P | PASS |
Pat Lass
|
|
|
daniel; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
|
Final | 7/26/2005 | 7/26/2005 | 7/26/2005 | P | FAIL |
Bob Reichert
|
|
|
leon; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice on panel, 352.30(A) rnc shall be strapped within 3' of box, 210.8(A)(7) gfci shall be provided within 6' of laundry sink, 314.21 drywall shall be repaired, 313.23(A)(1) there shall be no screws in boxes, 314.25 boxes shall have covers, 314.17(C) nm cable shall be stapled within 8" of box, 406.5 cover plates shall seat against mounting surface, 430.107 jetted tub shall have access, BCC disposal shall be installed for final
|
Rough-In Permanent Service | 3/2/2005 | 3/2/2005 | 3/2/2005 | P | PASS |
Bob Reichert
|
|
|
leon ###-#### called contr and said they have to have app. plans on job. ric ok p/s u/g n ok 3/2/2005 2:05:33 PM
|