Final | 4/11/2005 | 4/11/2005 | 4/11/2005 | P | PASS |
Mike Kinnear
|
|
|
Thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok final
|
Final | 4/8/2005 | 4/11/2005 | 4/11/2005 | A | FAIL |
Bob Reichert
|
|
|
Thank you ; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called contr, left corr notice, 210.8 recpts in kitchen shall be gfci protected, 210.52(C)(1) recpts shall be placed so no point is over 24" along wall line, 352.30(A) rnc shall be supported within 3' of box BCC no code violations shall be retained. 4/11/2005 8:21:10 AM
|
Electrical Rough-In | 3/17/2005 | 3/17/2005 | 3/17/2005 | P | PASS |
Bob Reichert
|
|
|
corrections made, ric ok, called contr about wrong inspection, they will call for final ltr.
|
Electrical Rough-In | 3/16/2005 | 3/17/2005 | 3/17/2005 | A | FAIL |
Bob Reichert
|
|
|
Thank you; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH 314.17(C) cables shall be supported within 8" of box, 334.80 Ampacity shall be adjusted if more than 2 nm cables grouped at foamed hole,250.148(C) shall use ground screws in metal boxes, 314.20 boxes shall be flush with wood surface,110.12(C) damaged wire shall be replaced 3/17/2005 9:36:31 AM
|
Final | 3/17/2005 | 3/17/2005 | 3/17/2005 | P | CANC |
Bob Reichert
|
|
|
THANK YOU; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH see new inspect. 3/17/2005 2:41:31 PM
|
Temporary Service | 3/3/2005 | 3/4/2005 | 3/4/2005 | A | NH |
Bob Reichert
|
|
|
Thank you ; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called contr, burn-out house, can't find key, wrong lockbox. Told to call when open. 3/4/2005 7:55:04 AM
|
Temporary Service | 3/4/2005 | 3/4/2005 | 3/4/2005 | P | PASS |
Bob Reichert
|
|
|
THANK YOU; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH t/s u/g reconnect, ok, Called contr to put on clamp on riser 3/4/2005 2:19:22 PM
|